Ex signal calculator
5115B
- Redundancy measurement with 2 input signals
- Signal calculator with the four arithmetical operations
- Duplication of the input signal
- Input for RTD, Ohm, TC, mV, mA, and V
- Universal supply by AC or DC
Application
- Redundancy measurement of temperature by means of two sensors, where the secondary sensor takes over the measurement when a sensor error occurs on the primary sensor.
- Duplication of the input signal, e.g. from a temperature sensor or an analog process signal to two separate analog outputs.
- Signal calculator with four arithmetical operations: Addition, subtraction, multiplication and division.
- Example: Differential measurement:
(Input 1 * K1) - (Input 2 * K2) + K4 - Example: Average measurement:
(Input 1 * 0.5) + (Input 2 * 0.5) + K4 - Example: Different functions on the outputs:
Output 1 = input 1 - input 2, and Output 2 = input 1 + input 2 - I.S. safety barrier and power supply for 2-wire transmitters.
Technical characteristics
- Within a few seconds the user can program PR5115B to a selected application using the configuration program PReset.
- A green front LED indicates normal operation, sensor error on each sensor, and functional error.
- 5-port 3.75 kVAC galvanic isolation.
Mounting / installation
- Mounted vertically or horizontally on a DIN rail. As the devices can be mounted without any distance between neighboring units, up to 42 devices can be mounted per meter.
Note
- Not suitable for new installations requiring certification to the latest ATEX standards - see ATEX certificate DEMKO 00ATEX128567 and EU Declaration of Conformity for details.
Data sheet & Manuals
Data sheet
- 5115B.pdf
- Latest version
Manuals
- 5115V105_UK.pdf
- 5115V104_UK.pdf
- 5115V103.pdf
- Previous versions
- Latest version
Manuals in Russian
- 5115V105_RU.pdf
- 5115V104_RU.pdf
- Previous versions
- Latest version
Approvals & Certificates
ATEX certificate
- 5115B.pdf
- Latest version
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
EAC declaration
- EAC_EMC_declaration_Ex_3000_5000_6000_9000.pdf
- Latest version
EAC Ex certificate
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 5115DoC_EU_103_UK.pdf
- 5115DoC_EU_102_UK.pdf
- 5115DoC_EU_101_UK.pdf
- 5115DoC_EU_100_UK.pdf
- Previous versions
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
Order form
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
Weight approx. | 225 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | 2.1 W / 2.8 W (1 / 2 ch.) |
Max. power dissipation | 2.0 W |
Isolation voltage |
|
Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
PELV/SELV | IEC 61140 |
Response time |
|
Temperature input, programmable (0...90%, 100...10%) | 400 ms...60 s |
mA / V input (programmable) | 250 ms...60 s |
Programming | Loop Link |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.05% of selected range |
Updating time |
115 ms (temperature input)
75 ms (mA / V / mV input) |
Redundancy switch-over time | ≤ 400 ms |
Signal dynamics, input | 22 bit |
Signal dynamics, output | 16 bit |
Auxiliary voltages: Reference voltage | 2.5 VDC ±0.5% / 15 mA |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Common input specifications |
|
Max. offset | 50% of selected max. value |
RTD input |
|
RTD type | Pt46, Pt100, Ni100, Cu53, lin. R |
Cable resistance per wire | 10 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) | < ±1.0°C |
Sensor error current | Nom. 30 μA |
Current input |
|
Measurement range | 0...100 mA |
Min. measurement range (span) | 4 mA |
Input resistance: Supplied unit | Nom. 10 Ω + PTC 10 Ω |
Input resistance: Non-supplied unit | RSHUNT = ∞, VDROP < 6 V |
Voltage input |
|
Measurement range | 0...250 VDC |
Min. measurement range (span) | 5 mV |
Input resistance |
Nom. 10 MΩ (≤ 2.5 VDC)
Nom. 5 MΩ (> 2.5 VDC) Nom. 10 MΩ (mV input) |
mV input |
|
Measurement range | -150...+150 mV |
Output specifications
Current output |
|
Signal range | 0...20 mA |
Min. signal range | 10 mA |
Load (@ current output) | ≤ 600 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Current limit | ≤ 28 mA |
Sensor error indication | Programmable 0...23 mA |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Voltage output |
|
Signal range | 0...10 VDC |
Min. signal range | 500 mV |
Load (@ voltage output) | ≥ 500 kΩ |
Passive 2-wire mA output |
|
Signal range | 4...20 mA |
Load stability | ≤ 0.01% of span / 100 Ω |
Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
Max. external 2-wire supply | 29 VDC |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
ATEX | 2014/34/EU |
RoHS | 2011/65/EU |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals
ATEX | DEMKO 00ATEX128567, II (1) GD [EEx ia] IIC |
EAC Ex | EAEU KZ 7500361.01.01.08756 |
DNV Marine | TAA0000101 |
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.
You can expect to get a confirmed delivery date via email within 2 days after we have received your order.
As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
Dedicated Presale / Aftersales
|
Product reliability |
Product deployment
|
Smart products
Check out our range of communication interfaces
|