HART transparent driver
9107B
- 24 VDC supply via power rail or connectors
- Fast response time
- High active output load 725 Ohm / 20 mA
- Output line fault detection via status relay
- SIL2 certified via Full Assessment according to IEC 61508
Application
- 9107B is a 1- or 2-channel isolated 1:1 driver barrier for intrinsic safety applications.
- Operation and drive control of I/P converters, valves and indicators mounted in the hazardous area.
- Operation of HART devices is possible as the unit transmits HART communication signals bi-directionally.
- 9107B can be mounted in the safe area or in zone 2 / Cl. 1, div. 2 and transmit signals to zone 0, 1, 2 and zone 20, 21, 22 including mining / Class I/II/III, Div. 1, Gr. A-G.
- The PR 4500 displays the process value for each channel and can be used to define high and low limits for detection of loop current level. If these limits are exceeded, the status relay will activate.
- Dual channel versions can be used for signal splitter applications - 1 in and 2 out.
Advanced features
- The PR 4500 detachable displays and the green and red front LEDs indicate operation status for each channel.
- A tag number can be defined for each channel.
- Output line fault detection.
- In the 1-channel version the status relay can be used as a simple limit switch.
- Suitable for the use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics
- High galvanic isolation of 2.6 kVAC.
- High accuracy better than 0.1%.
- Continuous check of vital stored data for safety reasons.
Mounting
- The devices can be mounted vertically or horizontally without distance between neighbouring units.
Data sheet & Manuals
Data sheet
- 9107B.pdf
- Latest version
Manuals
- 9107V002_109_UK.pdf
- 9107V002_108_UK.pdf
- 9107V002_107_UK.pdf
- 9107V002_106_UK.pdf
- 9107V002_105_UK.pdf
- 9107BV002_104_UK.pdf
- 9107BV002_103_UK.pdf
- 9107BV002_102_UK.pdf
- 9107BV002_101_UK.pdf
- 9107BV001_100_UK.pdf
- 9107AV002_101_UK.pdf
- 9107AV002_100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 9107V002_109_RU.pdf
- 9107V002_108_RU.pdf
- 9107V002_107_RU.pdf
- 9107V002_106_RU.pdf
- 9107V002_105_RU.pdf
- 9107BV002_104_RU.pdf
- 9107BV002_103_RU.pdf
- 9107BV002_102_RU.pdf
- Previous versions
- Latest version
Manuals in Portuguese (Brazil)
- 9107V002_109_BR.pdf
- 9107V002_108_BR.pdf
- 9107V002_107_BR.pdf
- 9107V002_106_BR.pdf
- 9107V002_105_BR.pdf
- 9107BV002_104_BR.pdf
- 9107BV002_103_BR.pdf
- 9107BV002_102_BR.pdf
- Previous versions
- Latest version
Manuals in Korean
- 9107V002_109_KR.pdf
- 9107V002_108_KR.pdf
- 9107V002_107_KR.pdf
- Previous versions
- Latest version
Safety manual (SIL)
- 9107_Safety_Manual_V2R0.pdf
- Latest version
Approvals & Certificates
ATEX certificate
- 9107B_11ATEX0247X_issue3.pdf
- 9107B_11ATEX0247X_issue2.pdf
- 9107B_11ATEX0247X_issue1.pdf
- Previous versions
- Latest version
IECEx certificate
- 9107BIEC_110088X__issue2.pdf
- 9107BIEC_110088X__issue1.pdf
- 9107BIEC_110088X__issue0.pdf
- Previous versions
- Latest version
UKEX certificate
- 9107B_23UKEX0108X_issue0.pdf
- 9107B_21UKEX0173X_issue0.pdf
- Previous versions
- Latest version
CCC certificate
- 9107_CCC_2023_04.pdf
- 9107_CCC_2020_11.pdf
- Previous versions
- Latest version
KCs certificate
- 9107B_KCs_21_AV4BO_0170X_0171X.pdf
- Latest version
FM certificate
- 9106_9107_FM16US0465X_FM16CA0213X.pdf
- 9106_9107_FM.pdf
- Previous versions
- Latest version
INMETRO certificate
- 9107_INMETRO_230004X_issue0.pdf
- 9107_INMETRO_160002X_issue1.pdf
- 9107_INMETRO_160002X_issue0.pdf
- Previous versions
- Latest version
SIL certificate
- 9107_002_SIL.pdf
- Latest version
UL certificate
DNV marine certificate
- DNV_9xxx_4510_4511.pdf
- 9000_DoC_DNV.pdf
- Previous versions
- Latest version
ClassNK certificate
- ClassNK-TA24034M_91xx_92xx_94xx.pdf
- Latest version
EAC declaration
- EAC_EMC_declaration_Ex_3000_5000_6000_9000.pdf
- Latest version
EAC Ex certificate
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 9107DoC_EU_104_UK.pdf
- 9107DoC_EU_103_UK.pdf
- 9107DoC_EU_102_UK.pdf
- 9107DoC_EU_101_UK.pdf
- 9107DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 9107DoC_UKCA_100.pdf
- Latest version
Modbus configuration manual
- 9107_MCM_102.pdf
- 9107_MCM_100.pdf
- Previous versions
- Latest version
Assessment report
- AssessmentReport_PR_2312098_V1R0_Series_9000.pdf
- Latest version
FMEDA report
- PR_9106_9107_060319_R025_FMEDA_V2R1.pdf
- Latest version
ISO 13849 declaration
- 9107_ISO_13849_declaration.pdf
- Latest version
EMC data
- 9000_EMC_data.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
Order form
Environmental Conditions
Operating temperature | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ PR 4500 | 109 x 23.5 x 131 mm |
Weight approx. | 250 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage | 19.2...31.2 VDC |
Fuse | 1.25 A SB / 250 VAC |
Max. required power | ≤ 1.0 W / ≤ 1.8 W (1 ch. / 2 ch.) |
Max. power dissipation, 1 / 2 ch. | ≤ 1.0 W / ≤ 1.8 W |
Isolation voltage |
|
Test /working: Input to any | 2.6 kVAC / 300 VAC reinforced isolation |
Analog output to supply | 2.6 kVAC / 300 VAC reinforced isolation |
Status relay to supply | 1.5 kVAC / 150 VAC reinforced isolation |
Response time |
|
Response time (0...90%, 100...10%) | < 5 ms |
Programming | PR 4500 communication interfaces |
Signal dynamics, input | Analog signal chain |
Signal dynamics, output | Analog signal chain |
HART bi-directional communication frequency range | 0.5...7.5 kHz |
Signal / noise ratio | > 60 dB |
Accuracy | Better than 0.1% of sel. range |
mA, absolute accuracy | ≤ ±16 μA |
mA, temperature coefficient | ≤ ±1.6 μA / °C |
Effect of supply voltage change on output (nom. 24 VDC) | < ±10 μA |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Current input |
|
Measurement range | 3.5...23 mA |
Sensor error detection: Loop break 4...20 mA | < 1 mA |
Input voltage drop, supplied unit | < 2 V @ 23 mA |
Input voltage drop, non-supplied unit | < 4 V @ 23 mA |
Output specifications
Current output |
|
Signal range | 3.5...23 mA |
Load (@ current output) | ≤ 725 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Current limit | ≤ 28 mA |
Status relay |
|
Relay function | N.C. |
Programmable low setpoint | 0...29.9 mA |
Programmable high setpoint | 0...29.9 mA |
Hysteresis for setpoints | 0.1 mA |
Max. voltage | 125 VAC / 110 VDC |
Max. current | 0.5 AAC / 0.3 ADC |
Max. voltage - hazardous installation | 32 VDC / 32 VAC |
Max. current - hazardous installation | 1 ADC / 0.5 AAC |
of span | = normal measurement range 4...20 mA |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
EAC LVD | TR-CU 004/2011 |
Approvals
ATEX | DEKRA 11ATEX0247 X |
IECEx | DEK 11.0088X |
UKEX |
DEKRA 21UKEX0173X
DEKRA 23UKEX0108X |
c FM us | FM16US0465X / FM16CA0213X |
INMETRO | DEKRA 23.0004X |
c UL us, UL 61010-1 | E314307 |
c UL us, UL 913 | E233311 (only 9107xx-U9) |
CCC | 2020322304003422 |
KCs | 21_AV4BO_0170X / 21_AV4BO_0171X (only 9107Bx-KCs) |
EAC Ex | EAEU KZ 7500361.01.01.08756 |
DNV Marine | TAA00000JD |
ClassNK | TA24034M |
SIL | SIL 2 certified & fully assessed acc. to IEC 61508 |
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.
You can expect to get a confirmed delivery date via email within 2 days after we have received your order.
As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
Dedicated Presale / Aftersales
|
Product reliability |
Product deployment
|
Smart products
Check out our range of communication interfaces
|