Universal transmitter
4116
- Input for RTD, TC, Ohm, potentiometer, mA and V
- 2-wire supply > 16 V
- FM-approved for installation in Div. 2
- Output for current, voltage and 2 relays
- Universal AC or DC supply
Application
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with 2 pairs of potential-free relay contacts and analog output.
- Galvanic separation of analog signals and measurement of floating signals.
- The 4116 is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
- Suitable for the use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics
- When 4116 is used in combination with the PR 4500 display series, all operational parameters can be modified to suit any application. As the 4116 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green / red front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
- Continuous check of vital stored data for safety reasons.
- 4-port 2.3 kVAC galvanic isolation.
Mounting / installation / programming
- Very low power consumption means units can be mounted side by side without an air gap – even at 60°C ambient temperature.
- Configuration, monitoring, 2-point process calibration and more are accomplished using PR's 4500 series of detachable displays.
- All programming can be password-protected.
Data sheet & Manuals
Data sheet
- 4116.pdf
- Latest version
Manuals
- 4116V106_UK.pdf
- 4116V105_UK.pdf
- 4116V104_UK.pdf
- 4116V103_UK.pdf
- 4116V102_UK.pdf
- 4116V101_UK.pdf
- 4116V100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 4116V106_RU.pdf
- 4116V105_RU.pdf
- 4116V104_RU.pdf
- 4116V103_RU.pdf
- 4116V102_RU.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 4116DoC_EU_103_UK.pdf
- 4116DoC_EU_102_UK.pdf
- 4116DoC_EU_101_UK.pdf
- 4116DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 4116DoC_UKCA_100_UK.pdf
- Latest version
Modbus configuration manual
- 4116_MCM_103.pdf
- 4116_MCM_102.pdf
- 4116_MCM_101.pdf
- 4116_MCM_100.pdf
- Previous versions
- Latest version
FMEDA report
- PR_4116_V2R4.pdf
- Latest version
ISO 13849 declaration
- 4116_ISO_13849_declaration.pdf
- Latest version
EMC data
- 4000_EMC_data.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
- SN4000_1_107_2420.pdf
- SN4000_1_106_2109.pdf
- SN4000_105_2001.pdf
- SN4000_104_1741.pdf
- SN4000_103_1613.pdf
- SN4000_102_1506.pdf
- Previous versions
- Latest version
Approvals & Certificates
FM certificate
- 4104_14_16_31_4222_FM.pdf
- Latest version
SIL certificate
- 411x_SILConformity03.pdf
- Latest version
UL certificate
- 4114_4116_4131_4222_UL.pdf
- Latest version
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
DNV EU-RO marine approval
- DNV_EU_RO_4114_4116_4131_5714_5715_5725.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
EAC LVD declaration
- EAC_LVD-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Download CAD-files
Order form
Environmental Conditions
Operating temperature | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ PR 4500 | 109 x 23.5 x 131 mm |
Weight approx. | 175 g |
Weight incl. 4501 / 451x (approx.) | 190 g / 205 g |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 2.5 W |
Max. power dissipation | ≤ 2.5 W |
Isolation voltage |
|
Test voltage | 2.3 kVAC |
Working voltage | 250 VAC (reinforced) / 500 VAC (basic) |
Response time |
|
Temperature input (0...90%, 100...10%) | ≤ 1 s |
mA / V input (0...90%, 100...10%) | ≤ 400 ms |
Auxiliary supplies |
|
2-w. supply (term. 44...43) | 25...16 VDC / 0...20 mA |
Programming | PR 4500 communication interfaces |
Signal dynamics, input | 24 bit |
Signal dynamics, output | 16 bit |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
RTD input |
|
RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
Cable resistance per wire | 50 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Short circuit detection | < 15 Ω |
Linear resistance input |
|
Linear resistance min....max. | 0 Ω...10000 Ω |
Potentiometer input |
|
Potentiometer min....max. | 10 Ω...100 kΩ |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) via ext. sensor in 5910 | 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C |
CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input |
|
Measurement range | 0...23 mA |
Programmable measurement ranges | 0...20 and 4...20 mA |
Input resistance | Nom. 20 Ω + PTC 50 Ω |
Sensor error detection: Loop break 4...20 mA | Yes |
Voltage input |
|
Measurement range | 0...12 VDC |
Programmable measurement ranges | 0/0.2...1, 0/1...5, 0/2...10 VDC |
Input resistance | Nom. 10 MΩ |
Output specifications
Current output |
|
Signal range | 0...23 mA |
Programmable signal ranges | 0...20/4...20/20...0/20...4 mA |
Load (@ current output) | ≤ 800 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | 0 / 3.5 / 23 mA / none |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Output limitation, on 4...20 and 20...4 mA signals | 3.8...20.5 mA |
Output limitation, on 0...20 and 20...0 mA signals | 0...20.5 mA |
Current limit | ≤ 28 mA |
Voltage output |
|
Signal range | 0...10 VDC |
Programmable signal ranges | 0/0.2...1; 0/1...5 ; 0/2...10; 1...0.2/0; 5...1/0; 10...2/0 V |
Load (@ voltage output) | ≥ 500 kΩ |
Relay output |
|
Relay functions | Setpoint, Window, Sensor error, Latch, Power and Off |
Max. voltage | 250 VAC / VDC |
Max. current | 2 A |
Max. AC power | 500 VA |
Max. DC current, resistive load > 30 VDC | See manual for details |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC LVD | TR-CU 004/2011 |
Approvals
c UL us, UL 508 | E231911 |
FM | 3025177 |
DNV Marine | TAA0000101 |
EU RO MR Type Approval | MRA000000Z |
SIL | Hardware assessed for use in SIL applications |
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.
You can expect to get a confirmed delivery date via email within 2 days after we have received your order.
As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
Dedicated Presale / Aftersales
|
Product reliability |
Product deployment
|
Smart products
Check out our range of communication interfaces
|