2-wire HART 7 temperature transmitter
6437D
- RTD, TC, potentiometer, linear resistance and bipolar mV input
- Single or true dual inputs with sensor redundancy and drift detection
- Wide ambient operating temperature of -50 to +85°C
- Total accuracy from 0.014%
- 2.5 kVAC galvanic isolation
- Full assessment to IEC61508 : 2010 for use in SIL 2/3 applications
Application
- Temperature measurement of a wide range of TC and RTD types.
- Conversion of wide span linear resistance and potentiometer inputs to 4...20 mA.
- Conversion of bipolar mV signals to 4...20 mA.
- Integration into asset management schemes.
- Critical applications requiring superior accuracy and/or sensor redundancy and drift detection.
Technical characteristics
- True dual input transmitter, accepts the widest range of dual input combinations.
- Sensor redundancy - output automatically switches to secondary sensor in event of primary sensor failure, maintaining uptime.
- Sensor drift detection - alerts when sensor differential exceeds user-defined limits, for maintenance optimization.
- Dynamic variable mapping for process data in addition to the primary variable e.g. dual input features such as average, differential and min./max. tracking.
- Groundbreaking digital and analog signal accuracy over full input span and ambient conditions.
- Extensive sensor matching including Callendar Van Dusen and custom linearizations.
- Programmable input limits with runtime metering ensure maximum process traceability and sensor out of range protection.
- IEC 61508 : 2010 full assessment up to SIL 3 together with enhanced EMC Functional Safety testing to IEC 61236-3-1.
- 6437xxSx is suitable for the use in systems up to Performance Level “d” according to ISO-13849
- Meets NAMUR NE21, NE43, NE44, NE89 and NE107 compliant diagnostics information.
Mounting / installation / programming
- DIN rail mounting with up to 84 inputs per meter.
- Configuration via PReset using PR5909 Loop Link / HART modem, or by Asset Management tool (e.g. Pactware, AMS, HART communicator).
- The 6437D can be mounted in zone 0, 1, 2 and zone 21, 22 including M1 / Class I, Division 1, Groups A, B, C, D.
Data sheet & Manuals
Data sheet
- 6437D.pdf
- Latest version
Manuals
- 6437V103_UK.pdf
- 6437V102_UK.pdf
- 6437V101_UK.pdf
- 6437V100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 6437V103_RU.pdf
- 6437V102_RU.pdf
- 6437V101_RU.pdf
- 6437V100_RU.pdf
- Previous versions
- Latest version
Safety manual (SIL)
Approvals & Certificates
ATEX certificate
- 6437D_16ATEX0047X_issue5.pdf
- 6437D_16ATEX0047X_issue4.pdf
- 6437D_16ATEX0047X_issue3.pdf
- 6437D_16ATEX0047X_issue2.pdf
- 6437D_16ATEX0047X_issue1.pdf
- Previous versions
- Latest version
IECEx certificate
- 6437DIEC_160029X_issue5.pdf
- 6437DIEC_160029X_issue4.pdf
- 6437DIEC_160029X_issue3.pdf
- 6437DIEC_160029X_issue2.pdf
- 6437DIEC_160029X_issue1.pdf
- Previous versions
- Latest version
CSA certificate
- 54xx_64xx_CSA_70066266.pdf
- Latest version
FM certificate
- 54xx_64xx_FM16US0287X_FM16CA0146X.pdf
- Latest version
INMETRO certificate
- INMETRO_54xx_64xx_issue3.pdf
- Latest version
NEPSI certificate
- 643x_NEPSI.pdf
- Latest version
SIL certificate
- 5437_6437_V01xxxx_SIL.pdf
- Latest version
DNV marine certificate
- DNV_EU_RO_5437_6437.pdf
- Latest version
EAC declaration
- EAC_EMC_declaration_Ex_3000_5000_6000_9000.pdf
- Latest version
EAC Ex certificate
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Belarus
- MPA_Belarus.pdf
- Latest version
Metrology Pattern Approval (MPA), Kazakhstan
- MPA_Kazakhstan.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 6437DoC_EU_101_UK.pdf
- 6437DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 6437DoC_UKCA_100_UK.pdf
- Latest version
CCC statement
- 5000_6000_series_CCC_statement.pdf
- Latest version
Assessment report
- AssessmentReport_5437_6437_V2R2.pdf
- Latest version
FMEDA report
- FMEDA_PR_6437_V1R0.pdf
- Latest version
ISO 13849 declaration
- 6437xxSx_ISO_13849_declaration.pdf
- Latest version
Field device specification
- 6437_FieldDeviceSpecification_V6R0.pdf
- Latest version
HART certificate
- 5437_6437_HART_7_certificate.pdf
- Latest version
EMC data
- 5437_6437_EMC_data.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
- SN6437_103_2240.pdf
- SN6437_102_2114.pdf
- SN6437_101_2106.pdf
- SN6437_100_1924.pdf
- Previous versions
- Latest version
Download Software
Order form
Environmental Conditions
Operating temperature |
-50°C to +85°C (standard)
-40°C to +80°C (SIL) |
Storage temperature | -50°C to +85°C |
Calibration temperature | 23...25°C |
Relative humidity | < 99% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Weight (single input / dual input) | |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
DIN rail type | DIN EN 60715/35 mm |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...25 Hz | ±1.6 mm |
25...100 Hz | ±4 g |
Common specifications
Supply |
|
Supply voltage | 7.5*...30** VDC |
Power dissipation, per channel | ≤ 850 mW |
Additional min. supply voltage when using test terminals | 0.8 V |
Min. load resistance at >37 V supply | (Vsupply – 37) / 23 mA |
Isolation voltage |
|
Isolation voltage, test / working | 2.5 kVAC / 42 VAC |
Response time |
|
Response time | 75 ms |
Programmable damping | 0...60 s |
Polarity protection | All inputs and outputs |
Warm-up time | < 5 min. |
Start-up time | < 2.75 s |
Programming | Loop Link & HART |
Write protection | Jumper or software |
Signal / noise ratio | > 60 dB |
Long-term stability, better than | ±0.05% of span / year (±0.18% of span / 5 years) |
Signal dynamics, input | 24 bit |
Signal dynamics, output | 18 bit |
Effect of supply voltage change | < 0.005% of span / VDC |
Accuracy | See manual for details |
EMC immunity influence | < ±0.1% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% |
Input specifications
RTD input |
|
RTD type | Pt10...10000, Ni10...10000, Cu5...1000 |
Basic accuracy, e.g. Pt100 | ≤ ±0.04°C |
Cable resistance per wire | 50 Ω (max.) |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor current | < 0.15 mA |
Sensor error detection | None, Shorted, Broken, Shorted or Broken |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Basic accuracy, e.g. TC K | ≤ ±0.25°C |
Cold junction compensation (CJC) | Constant, internal or external via a Pt100 or Ni100 sensor |
Sensor error detection | None, Shorted, Broken, Shorted or Broken |
Linear resistance input |
|
Measurement range / min. range (span) | 0 Ω...100 kΩ / 25 Ω |
Cable resistance per wire (max.) | 50 Ω |
Sensor current | < 0.15 mA |
Sensor error detection | None, Broken |
Potentiometer input |
|
Potentiometer min....max. | 10 Ω...100 kΩ |
Measurement range / min. range (span) | 0...100% / 10% |
Cable resistance per wire (max.) | 50 Ω |
Sensor current | < 0.15 mA |
Sensor error detection | None, Shorted, Broken, Shorted or Broken |
mV input |
|
Measurement range |
-800...+800 mV (bipolar)
-100 to 1700 mV |
Min. measurement range (span) | 2.5 mV |
Input resistance | 10 MΩ |
Sensor error detection | None, Broken |
Output specifications
Common output specifications |
|
Normal range, programmable | 3.8...20.5 / 20.5...3.8 mA |
Extended range (output limits), programmable | 3.5...23 / 23...3.5 mA |
Basic accuracy | ≤ ±1.6 μA (0.01% of full output span) |
Updating time | 10 ms |
Load (@ current output) | ≤ (Vsupply -7.5)/0.023 [Ω] |
Load stability | < 0.01% of span / 100 Ω |
Sensor error indication | Programmable 3.5…23 mA |
NAMUR NE 43 Upscale/Downscale | > 21 mA / < 3.6 mA |
HART protocol revisions | HART 7 and HART 5 |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals
ATEX | DEKRA 16ATEX0047X |
IECEx | IECEx DEK. 16.0029X |
CSA | CSA 16.70066266 |
c FM us | FM16US0287X / FM16CA0146X |
INMETRO | DEKRA 16.0008 X |
NEPSI | GYJ18.1057X |
EAC Ex | EAEU KZ 7500361.01.01.08756 |
EU RO MR Type Approval | MRA0000023 |
SIL | SIL 2 / SIL 3 certified & fully assessed acc. to IEC 61508 |
NB
* / ** | See manual for details |
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.
You can expect to get a confirmed delivery date via email within 2 days after we have received your order.
As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
Dedicated Presale / Aftersales
|
Product reliability |
Product deployment
|
Smart products
Check out our range of communication interfaces
|