Loop powered isolator

 

3185

 

  • 1 or 2 channel input loop powered isolator
  • Signal 1:1 functional range 0...23 mA
  • Low input voltage drop and fast response time
  • Excellent accuracy and high load stability
  • Slimline 6.1 mm housing
Zone2 Ex Iec Iecex Zone2 Fmapprovedcus Zone2 UL List CCC DNV Eac Ex Mpa EAC UKCA CE Pr Rohs Guarantee
  1. Overview + -

  2. Technical details + -

  3. Accessories + -

  4. Order and delivery + -

  5. Why choose PR + -

Application

  • 1:1 input loop powered isolator of current signals in the range 0(4)...20 mA.
  • 3185 is an easy mounting DIN rail unit.
  • A very competitive choice in terms of both price and technology for galvanic isolation of current signals.
  • Provides surge suppression and protects control systems from transients and noise.
  • 3185 eliminates ground loops and can be used for measuring floating signals.
  • The device can be mounted in Safe area or in Zone 2 and Cl. 1 Div 2. area.

Technical characteristics

  • 3185 is powered by the analog input current signal loop.
  • Low input voltage drop, typ 1.35 V + Vout.
  • Excellent conversion accuracy, better than 0.1% in the range 0…20.5 mA.
  • Functional range is 0...23 mA which means that 3185 is NAMUR NE43 compliant.
  • Inputs and outputs are floating and galvanically separated.
  • The output is voltage limited to 17.5 VDC.
  • High galvanic isolation of 2.5 kVAC.
  • Fast response time < 5 ms.
  • Excellent signal/noise ratio > 60 dB.

Mounting / installation / programming

  • DIN rail mounting with up to 330 channels per meter.
  • Temperature operation range is from -25...+70°C.

Data sheet & Manuals


Data sheet

Manuals

Manuals in Russian

Approvals & Certificates


ATEX certificate

IECEx certificate

UKEX certificate

CCC certificate

FM certificate

UL certificate

DNV marine certificate

EAC declaration

EAC Ex certificate

Metrology Pattern Approval (MPA), Russia

Supplementary documentation


EU Declaration of Conformity

UKCA Declaration of Conformity

EMC data

Environmental Conditions

Operating temperature -25°C to +70°C
Storage temperature -40°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 113 x 6.1 x 115 mm
Weight approx. 70 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.5 mm2 / AWG 26...12 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...25 Hz ±1.6 mm
25...100 Hz ±4 g

Common specifications

Supply

Power dissipation, per channel 30 mW

Isolation voltage

Isolation voltage, test / working 2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2 250 VAC

Response time

Response time (0...90%, 100...10%) < 5 ms
Signal / noise ratio > 60 dB
Signal dynamics, input Analog signal chain
Signal dynamics, output Analog signal chain
Accuracy Better than 0.1%
Cut-off frequency (3 dB) 100 Hz
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

Current input

Measurement range 0...23 mA
Input voltage drop (Unit voltage drop) + Vout.
Signal conversion 1:1
Start-up current, typ. 10 uA
Current input overload, max. 50 mA
Input to output voltage drop, typ. 1.35 V + (0.015 x Vout.)

Output specifications

Current output

Signal range 0...23 mA
Load (@ current output) ≤ 600 Ω
Load stability < 0.01% of span / 100 Ω
Voltage limit 17.5 V
of span = 0...20 mA

I.S. / Ex marking

ATEX II 3 G Ex ec IIC T4 Gc
IECEx Ex ec IIC T4 Gc
FM, US Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4
FM, CA Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4
EAC Ex 2Ex nA IIC T4 Gc X

Observed authority requirements

EMC 2014/30/EU & UK SI 2016/1091
LVD 2014/35/EU & UK SI 2016/1101
ATEX 2014/34/EU & UK SI 2016/1107
RoHS 2011/65/EU & UK SI 2012/3032
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011

Approvals

ATEX KEMA 10ATEX0147 X
IECEx KEM 10.0068X
UKEX DEKRA 21UKEX0055X
c FM us FM17US0004X / FM17CA0003X
c UL us, UL 61010-1 E314307
CCC 2020322310003554
DNV Marine TAA00001RW
EAC Ex EAEU KZ 7500361.01.01.08756

 

Need support to select the right product for your application?

Our sales engineers are ready to help specify the right device to meet your needs.

 

Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.

 

You can expect to get a confirmed delivery date via email within 2 days after we have received your order.

 

As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.

 

State-of-the-art manufacturing

State-of-the-art manufacturing

Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down.

 

Dedicated Presales / Aftersales

Dedicated Presale / Aftersales
Our more than 80 dedicated sales engineers can help specify the right device for your application. Backed by our 9 subsidiaries and more than 40 dedicated partners, we are directly accessible in more than 40 countries around the world.

 

Find a PR location close to you

 

Product reliability

Product reliability
Although we’d always like to be top of mind, we recognize our job is mainly to provide peace of mind. Install & Forget® is our way of saying that once installed, our devices will continue to perform even in the toughest environments. And we are not afraid to back that statement up with commitments.

 

Product deployment

Product deployment
Our devices are intuitive and simple to configure. Once installed they visualize rich diagnostics data, allowing the operator to plan preventative maintenance, maximizing process up-time.

 

 

Smart products

Smart products
Many of our devices are designed to accommodate current and future communication enablers, providing the operator with multifunctional capabilities that extends into the future.

 

Check out our range of communication interfaces

 

Smart products

 

Your request has been sent successfully. 0 items on your list
Your contact information

Company information

Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country

Your information

Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please read and agree with PR electronics’ Privacy Policy.
Get an answer within 24 hours
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

A mistake has occurred. Please call us instead

You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.
Contact us

If you need support, you are always welcome to contact us

Contact us
Newsletter Icon Red

Register here to receive our newsletter

Newsletter Icon Red