Power connector unit
3405
- Slimline housing of 6.1 mm
- Supplies DIN rail from supply terminals
- Can pass up to 2.5 A
- Up to 100 units can be powered
Applications
- Power can be connected to the DIN rail from supply terminals.
- Alternatively a powered DIN rail can supply power to the terminals.
- Installation in ATEX Ex zone 2 / IECEx zone 2 / FM division 2.
- Suitable for environments with high vibration stress, e.g. ships.
Technical characteristics
- 3405 can pass up to 2.5 A
- With 3405, up to 92 units can be powered (depending on the PR product type).
Data sheet & Manuals
Approvals & Certificates
ATEX certificate
- 3405_issue12.pdf
- Latest version
IECEx certificate
- 3405IEC_issue 11.pdf
- Latest version
UKEX certificate
- 3405UKEX_Issue1.pdf
- Latest version
CCC certificate
- 3000_series_CCC_2023_04.pdf
- 3000_series_CCC_2020_12.pdf
- Previous versions
- Latest version
FM certificate
- 3xxx_FM17CA0003X_US0004X.pdf
- 3xxx_FM_3041043_C.pdf
- Previous versions
- Latest version
UL certificate
- 3103-09_3117-18_3405.pdf
- Latest version
DNV marine certificate
- DNV_3xxx_TAA00001RW.pdf
- Latest version
EAC declaration
- EAC_EMC_declaration_Ex_3000_5000_6000_9000.pdf
- Latest version
EAC Ex certificate
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 3405DoC_EU_105_UK.pdf
- 3405DoC_EU_104_UK.pdf
- 3405DoC_EU_103_UK.pdf
- 3405DoC_EU_102_UK.pdf
- 3405DoC_EU_101_UK.pdf
- 3405DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 3405DoC_UKCA_100_UK.pdf
- Latest version
Safety note
Safety note
Order form
Environmental Conditions
Operating temperature | -25°C to +70°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 113 x 6.1 x 115 mm |
Weight approx. | 65 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.5 mm2 / AWG 26...12 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...25 Hz | ±1.6 mm |
25...100 Hz | ±4 g |
Common specifications
Supply |
|
Supply voltage | 16.8...31.2 VDC |
Internal power dissipation | 0.25 W (max.) |
Required external fuse | 2.5 A |
I.S. / Ex marking
ATEX | II 3 G Ex ec IIC T4 Gc |
IECEx | Ex ec IIC T4 Gc |
FM, US | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4 |
FM, CA | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4 |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals
ATEX | KEMA 10ATEX0147 X |
IECEx | KEM 10.0068X |
UKEX | DEKRA 21UKEX0055X |
c FM us | FM17US0004X / FM17CA0003X |
c UL us, UL 61010-1 | E314307 |
EAC Ex | EAEU KZ 7500361.01.01.08756 |
DNV Marine | TAA00001RW |
CCC | 2020322310003554 |
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.
You can expect to get a confirmed delivery date via email within 2 days after we have received your order.
As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
Dedicated Presale / Aftersales
|
Product reliability |
Product deployment
|
Smart products
Check out our range of communication interfaces
|