2-wire programmable transmitter
5131A
- Input for RTD, TC, mV, linear resistance, mA, and V
- 3.75 kVAC galvanic isolation
- 4...20 mA loop output
- 1- or 2-channel version
- DIN rail mounting
Overview
Advanced features
- The 5131A transmitter can be configured with the software program PReset using a standard PC and the Loop Link communications unit.
Application
- Independent channel jumper selectable inputs for current/voltage or temperature.
- Current input programmable in range 0...100 mA and voltage inputs in range 0...250 VDC.
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, for example from solenoids and butterfly valves or linear movements with attached potentiometer.
- 4- or 3-wire connection automatic cable compensation or 2-wire connection with programmable cable compensation.
- Configurable sensor error detection including NAMUR NE43.
Technical characteristics
- The 2-channel version has full galvanic isolation between the channels.
- Separation of circuits in PELV/SELV installations.
Data sheet & Manuals
Data sheet
- 5131A.pdf
- Latest version
Manuals
- 5131V105_UK.pdf
- 5131V104_UK.pdf
- 5131V103.pdf
- Previous versions
- Latest version
Manuals in Russian
- 5131V105_RU.pdf
- 5131V104_RU.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 5131DoC_EU_103_UK.pdf
- 5131DoC_EU_102_UK.pdf
- 5131DoC_EU_101_UK.pdf
- 5131DoC_EU_100_UK.pdf
- Previous versions
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
Approvals & Certificates
EAC declaration
- EAC-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Order form
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
Weight approx. | 195 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Common specifications
Supply |
|
Supply voltage | 7.5...35 VDC |
Fuse | 50 mA SB / 250 VAC |
Isolation voltage |
|
Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
PELV/SELV | IEC 61140 |
Response time |
|
Temperature input, programmable (0...90%, 100...10%) | 400 ms...60 s |
mA / V input (programmable) | 250 ms...60 s |
Programming | Loop Link |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Signal dynamics, input | 22 bit |
Signal dynamics, output | 16 bit |
Updating time |
115 ms (temperature input)
75 ms (mA / V / mV input) |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Effect of supply voltage change | < 0.005% of span / VDC |
Input specifications
Common input specifications |
|
Max. offset | 50% of selected max. value |
RTD input |
|
RTD type | Pt100, Ni100, lin. R |
Cable resistance per wire | 10 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) | < ±1.0°C |
Sensor error current | Nom. 30 μA |
Sensor error detection | Yes |
Current input |
|
Measurement range | 0...100 mA |
Min. measurement range (span) | 4 mA |
Input resistance: Supplied unit | Nom. 10 Ω + PTC 10 Ω |
Input resistance: Non-supplied unit | RSHUNT = ∞, VDROP < 6 V |
mV input |
|
Measurement range | -150...+150 mV |
Voltage input |
|
Measurement range | 0...250 VDC |
Min. measurement range (span) | 5 mV |
Input resistance |
Nom. 10 MΩ (≤ 2.5 VDC)
Nom. 5 MΩ (> 2.5 VDC) |
Output specifications
Current output |
|
Signal range | 4…20 mA |
Min. signal range | 10 mA |
Load (@ current output) | ≤ (Vsupply - 7.5) / 0.023 [Ω] |
Load stability | ≤ 0.01% of span / 100 Ω |
Current limit | ≤ 28 mA |
Sensor error indication | Programmable 3.5…23 mA |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
RoHS | 2011/65/EU |
EAC | TR-CU 020/2011 |
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.
You can expect to get a confirmed delivery date via email within 2 days after we have received your order.
As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
Dedicated Presale / Aftersales
|
Product reliability |
Product deployment
|
Smart products
Check out our range of communication interfaces
|