PR default configurations

Environmental Conditions

Operating temperature -20°C to +60°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 130 mm
Weight approx. 235 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
Fuse 400 mA SB / 250 VAC
Max. required power 2.4 W
Max. power dissipation 2.0 W

Isolation voltage

Isolation voltage, test / working 3.75 kVAC / 250 VAC
PELV/SELV IEC 61140

Response time

Temperature input, programmable (0...90%, 100...10%) 400 ms...60 s
mA / V input (programmable) 250 ms...60 s

Auxiliary supplies

2-wire supply (pin 54...52) 28...16.5 VDC / 0...20 mA
Programming Loop Link
Signal / noise ratio Min. 60 dB (0...100 kHz)
Accuracy Better than 0.05% of selected range
Signal dynamics, input 22 bit
Signal dynamics, output 16 bit
Auxiliary voltages: Reference voltage 2.5 VDC ±0.5% / 15 mA
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

Common input specifications

Max. offset 50% of selected max. value

RTD input

RTD type Pt46, Pt100, Ni100, Cu53, lin. R
Cable resistance per wire 10 Ω (max. 50 Ω)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) < ±1.0°C
Sensor error current Nom. 30 μA
Sensor error detection Yes

Current input

Measurement range 0...100 mA
Min. measurement range (span) 4 mA
Input resistance: Supplied unit Nom. 10 Ω + PTC 10 Ω
Input resistance: Non-supplied unit RSHUNT = ∞, VDROP < 6 V
Sensor error detection Loop break 4...20 mA

Voltage input

Measurement range 0...250 VDC -2500...+2500 mV
Min. measurement range (span) 5 mV
Input resistance Nom. 10 MΩ (≤ 2.5 VDC) Nom. 5 MΩ (> 2.5 VDC)
> 5 MΩ (mV input)
Potentiometer via 2.5 V ref. 170 Ω

Output specifications

Current output

Signal range 0...20 mA
Min. signal range 10 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limit ≤ 28 mA
Sensor error indication Programmable 0...23 mA
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA

Passive 2-wire mA output

Signal range 4...20 mA
Load stability ≤ 0.01% of span / 100 Ω
Max. external 2-wire supply 29 VDC
Effect of external 2-wire supply voltage variation < 0.005% of span / V

Voltage output

Signal range 0...10 VDC
Min. signal range 500 mV
Load (@ voltage output) ≥ 500 kΩ

Relay output

Relay functions Increasing / decreasing Window
Max. voltage 250 VAC / VDC
Max. current 2 A
Max. AC power 500 VA
Max. DC current, resistive load > 30 VDC See manual for details
Sensor error reaction Break / Make / Hold / None
of span = of the presently selected range

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011

Approvals

ATEX KEMA 04ATEX1316 X
FM FM21US0035X
c UL us, UL 508 E231911
EAC Ex RU C-DK.HA65.B.00355/19
DNV Marine TAA0000101
Your request has been sent successfully. 0 items on your list
Your contact information

Company information

Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country

Your information

Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please read and agree with PR electronics’ Privacy Policy.
Get an answer within 24 hours

A mistake has occurred. Please call us instead

You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.
Service Red

If you need support, you are always welcome to contact us

Service Red
Newsletter Icon Red

Register here to receive our newsletter

Newsletter Icon Red