Pulse isolator
5202B
- 2 channels - 2 or 4 outputs
- Dual output
- 5-port 3.75 kVAC galvanic isolation
- Cable error detection
- Universal supply by AC or DC
Application
- Pulse isolator with safety barrier for the supply of NAMUR sensors installed in the hazardous area.
- Pulse isolator with safety barrier for the detection of mechanical contacts installed in the hazardous area.
- One input signal can be used on two separate outputs.
- A cable error alarm can be detected on a separate output.
Technical characteristics
- PR5202B1 and 5202B2 have relays with change-over contacts or open NPN collectors available in the safe area.
- PR5202B4 has 4 SPST relays, which are activated simultaneously two and two, available in the safe area. Each relay can be programmed to the function N.O. or N.C.
- Inputs, outputs and supply are floating and galvanically separated.
- 5202B is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
Mounting / installation
- Mounted vertically or horizontally on a DIN rail. Up to 84 channels per meter can be mounted.
Note
- Not suitable for new installations requiring certification to the latest ATEX standards - see ATEX certificate DEMKO 99ATEX127186 and EU Declaration of Conformity for details.
Data sheet & Manuals
Data sheet
- 5202B.pdf
- Latest version
Manuals
- 5202V108_UK.pdf
- 5202V107_UK.pdf
- 5202BV106.pdf
- Previous versions
- Latest version
Manuals in Russian
- 5202V108_RU.pdf
- 5202BL107_RU.pdf
- Previous versions
- Latest version
Approvals & Certificates
ATEX certificate
- 5202B.pdf
- Latest version
SIL certificate
- 5202_SILConformity03.pdf
- Latest version
UL certificate
- 5202B_UL.pdf
- Latest version
EAC declaration
- EAC_EMC_declaration_Ex_3000_5000_6000_9000.pdf
- Latest version
EAC Ex certificate
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 5202DoC_EU_102_UK.pdf
- 5202DoC_EU_101_UK.pdf
- 5202DoC_EU_100_UK.pdf
- Previous versions
- Latest version
FMEDA report
- PR_5202_20050414_R002_V1_R1_1.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
- SN5000-3_103_1933.pdf
- SN5000-3_102_1613.pdf
- SN5000_101_1450.pdf
- Previous versions
- Latest version
Order form
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 130 mm |
Weight approx. | 230 g |
Wire size | 1 x 2.5 mm2 stranded wire |
Screw terminal torque | 0.5 Nm |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power |
≤ 1.5 W (2 channels), 5202B1 and 5202B2
≤ 2.0 W (2 channels), 5202B4 |
Internal power dissipation |
≤ 1.5 W (2 channels), 5202B1 and 5202B2
≤ 2.0 W (2 channels), 5202B4 |
Isolation voltage |
|
Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
PELV/SELV | IEC 61140 |
Auxiliary supplies |
|
NAMUR supply | 8 VDC / 8 mA |
EMC immunity influence | < ±0.5% |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% |
Input specifications
Sensor types | NAMUR according to EN 60947-5-6 / mechanical contact |
Frequency range | 0...5 kHz |
Pulse length | > 0.1 ms |
Input resistance | 1 kΩ |
Trig level, signal | < 1.2 mA, > 2.1 mA |
Trig level, cable fault | < 0.1 mA, > 6.5 mA |
Output specifications
Relay output |
|
Max. switching frequency | 20 Hz |
Max. voltage | 250 VRMS |
Max. current | 2 AAC |
Max. AC power | 100 VA |
Max. load at 24 VDC | 1 A |
NPN output |
|
Max. switching frequency | 5 kHz |
Min. pulse length | > 0.1 ms |
Max. load, current / voltage | 80 mA / 30 VDC |
Voltage drop at 25 mA / 80 mA | < 0.75 VDC / < 2.5 VDC |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
EAC | TR-CU 020/2011 |
Approvals
ATEX | DEMKO 99ATEX127186, II (1) GD [EEx ia] IIC |
c UL us, UL 913 | E233311 |
EAC Ex | RU C-DK.HA65.B.00355/19 |
SIL | Hardware assessed for use in SIL applications |
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.
You can expect to get a confirmed delivery date via email within 2 days after we have received your order.
As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
Dedicated Presale / Aftersales
|
Product reliability |
Product deployment
|
Smart products
Check out our range of communication interfaces
|