3118
Data sheet & Manuals
Safety note
Safety note
Approvals & Certificates
CCC certificate
- 3000_series_CCC_2023_04.pdf
- 3000_series_CCC_2020_12.pdf
- Previous versions
- Latest version
FM certificate
- 3xxx_FM17CA0003X_US0004X.pdf
- 3xxx_FM_3041043_C.pdf
- Previous versions
- Latest version
UL certificate
- 3103-09_3117-18_3405.pdf
- Latest version
DNV marine certificate
- DNV_3xxx_TAA00001RW.pdf
- Latest version
EAC declaration
- EAC_EMC_declaration_Ex_3000_5000_6000_9000.pdf
- Latest version
EAC Ex certificate
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
EMC data
- 3000_EMC_data.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Environmental Conditions
Operating temperature | -25°C to +70°C |
Storage temperature | -40°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 113 x 6.1 x 115 mm |
Weight approx. | 70 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.5 mm2 / AWG 26...12 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...25 Hz | ±1.6 mm |
25...100 Hz | ±4 g |
Common specifications
Supply |
|
Supply voltage | 16.8...31.2 VDC |
Max. required power | ≤ 1.2 W |
Max. power dissipation | 0.43 W |
Isolation voltage |
|
Isolation voltage, test / working | 2.5 kVAC / 300 VAC (reinforced) |
Zone 2 / Div. 2 | 250 VAC |
Response time |
|
Response time (0...90%, 100...10%) | < 7 ms or < 44 ms |
MTBF, acc. to IEC 61709 (SN29500) | > 187 years |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Signal dynamics, input | Analog signal chain |
Signal dynamics, output | Analog signal chain |
Programming | DIP-switches |
Cut-off frequency (3 dB) | > 100 Hz or 10 Hz (selectable via DIP-switch) |
Accuracy | < ±0.05% of span |
Temperature coefficient | < ±0.01% of span / °C |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Current input |
|
Measurement range | -23...+23 mA |
Programmable measurement ranges | ± 10 and ± 20 mA |
Input voltage drop | < 1 VDC @ 23 mA |
Voltage input |
|
Measurement range | -11.5...+11.5 V |
Programmable ranges | ±5 and ±10 V |
Input resistance | ≥ 1 MΩ |
Output specifications
Current output |
|
Signal range | 0...23 mA |
Programmable signal ranges | 0 / 4...20 mA |
Bipolar wiring and programming set-up | ±10 and ± 20 mA |
Load (@ current output) | ≤ 300 Ω per channel |
Load stability | ≤ 0.002% of span / 100 Ω |
Current limit | ≤ 28 mA |
Voltage output |
|
Signal range | 0...10 VDC |
Programmable signal ranges | 0/1...5 and 0/2...10 V |
Load (@ voltage output) | ≥ 10 kΩ |
of span | = of the presently selected range |
I.S. / Ex marking
ATEX | II 3 G Ex ec IIC T4 Gc |
IECEx | Ex ec IIC T4 Gc |
FM, US | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4 |
FM, CA | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4 |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals
ATEX | KEMA 10ATEX0147 X |
IECEx | KEM 10.0068X |
UKEX | DEKRA 21UKEX0055X |
c FM us | FM17US0004X / FM17CA0003X |
c UL us, UL 61010-1 | E314307 |
CCC | 2020322310003554 |
EAC Ex | RU C-DK.HA65.B.00355/19 |
DNV Marine | TAA00001RW |