3225

 

Zone2 Ex Iec Iecex Zone2 UL List CCC UKCA CE Pr Rohs Guarantee
  1. Overview + -

  2. Technical details + -

  3. Accessories + -

Data sheet & Manuals


Data sheet

Manuals

Manuals in Russian

Approvals & Certificates


ATEX certificate

IECEx certificate

UKEX certificate

UL certificate

CCC certificate

Supplementary documentation


EU Declaration of Conformity

UKCA Declaration of Conformity

EMC data

PR default configurations

Safety note


Safety note

Environmental Conditions

Operating temperature -25°C to +70°C
Storage temperature -40°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 113 x 6.1 x 115 mm
Weight approx. 70 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.5 mm2 / AWG 26...12 stranded wire
Screw terminal torque 0.5 Nm

Common specifications

Supply

Supply voltage 16.8...31.2 VDC
Fuse 400 mA SB / 250 VAC
Max. required power ≤ 1.2 W
Max. power dissipation 0.65 W

Isolation voltage

Isolation voltage, test / working 2.5 kVAC / 300 VAC (reinforced)

Response time

Response time (0...90%, 100...10%) ≤ 30 ms

Auxiliary supplies

Sensor supply limitation 23 mA, 5…17 V
Signal dynamics, output 18 bit
Long term stability, current, 1yr / 5yr @ 25°C ≤ 0.058% / ≤ 0.101%
Long term stability, voltage, 1yr / 5yr @ 25°C ≤ 0.032% / ≤ 0.058%
Accuracy See manual for details
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

Frequency input

Frequency range 0.001 Hz to 100 kHz
Time range, time function 10 μs to 999.9 s
Max. frequency / min. pulse width, with input filter ON 75 Hz / 8 ms

Sensor specifications

Tacho, trig-level LOW / HIGH ≤ -50 mV / ≥ +50 mV
NPN / PNP, trig-level LOW / HIGH ≤ 4.0 V / ≥ 7.0 V
TTL, trig-level LOW / HIGH ≤ 0.8 V / ≥ 2.0 V
S0, trig-level LOW / HIGH ≤ 2.2 mA / ≥ 9.0 mA
NAMUR, trig-level LOW / HIGH ≤ 1.2 / ≥ 2.1 mA

Special voltage / current input

User-programmable trig-levels -0.05...6.50 V 0.0...10.0 mA

Output specifications

Current output

Signal range, active 0...23 mA
Programmable signal ranges 0 / 4...20 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.001% of span / 100 Ω
Response time, programmable 0.0...60.0 s
Sensor error indication 0 / 3.5 / 23 mA / none
Current limit ≤ 28 mA

Voltage output

Signal range ≤ 11.5 VDC
Programmable signal ranges 0...1; 0…5; 0...10; 0.2...1; 2…10 VDC
Load (@ voltage output) ≥ 10 kΩ
Response time, programmable 0.0...60.0 s

Relay output

Relay functions Setpoint, Window and Latch
Hysteresis 0...100%
ON and OFF delay 0...3600 s
Power On delay 0...9999 s
Sensor error reaction Break / Make / Hold
Max. voltage 250 VAC / 200 VDC
Max. current 2 A
Max. AC power 500 VA
Max. DC current, resistive load ≤ 30 VDC 2 ADC
Max. DC current, resistive load > 30 VDC See manual for details

Observed authority requirements

EMC 2014/30/EU & UK SI 2016/1091
LVD 2014/35/EU & UK SI 2016/1101
RoHS 2011/65/EU & UK SI 2012/3032
ATEX 2014/34/EU & UK SI 2016/1107

Approvals

ATEX KEMA 10ATEX0147 X
IECEx KEM 10.0068X
UKEX DEKRA 21UKEX0055X
c UL us, UL 61010-1 E314307
CCC 2020322310003554
Your request has been sent successfully. 0 items on your list
Your contact information

Company information

Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country

Your information

Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please read and agree with PR electronics’ Privacy Policy.
Get an answer within 24 hours

A mistake has occurred. Please call us instead

You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.
Service Red

If you need support, you are always welcome to contact us

Service Red
Newsletter Icon Red

Register here to receive our newsletter

Newsletter Icon Red