Universal frequency converter

 

3225

 

  • Input: NAMUR, NPN, PNP, Tacho, TTL, S0 & switches
  • Output: Universal mA / V or relay
  • 2.5 KVAC isolation
  • DIP-switch or display programmable
  • Power supply 16.8 VDC…31.2 VDC
Zone2 Ex Iec Iecex Zone2 UL List CCC UKCA CE Pr Rohs Guarantee
  1. Overview + -

  2. Technical details + -

  3. Accessories + -

  4. Order and delivery + -

  5. Why choose PR + -

Functional highlights

  • Measures frequencies up to 100 kHz.
  • Active current output.
  • Buffered voltage output 10 VDC.
  • 2-point process calibration. 
  • User-programmable trigger levels -0.05…6.5 V and sensor supply 5…17 V.
  • NAMUR sensor error detection.
  • Output relay with windows, setpoint and latch functionality. 
  • Simulation of process value during commissioning / maintenance.
  • Fast response time, with simultaneous sensor error detection (PATENTED). 
  • All terminals are over-voltage protected, polarity protected and short-circuit protected.

Technical highlights

  • Accuracy < 0.06% / span.
  • Response time < 30 ms.
  • 2.5 kVAC, 3-port galvanic isolation.
  • Wide ambient temperature range -25...70°C.
  • NAMUR NE21, NE43.

Programming

  • Easy configuration via DIP-switches.
  • Factory calibrated in all selectable measurement ranges.
  • Configuration, monitoring, and diagnostics using PR 4500 detachable communication interfaces via the PR 4590 ConfigMate.
  • All programming can be password protected.
  • Scrolling help text in 7 languages.

Mounting

  • Units can be mounted side by side, horizontally and vertically, without air gap on a standard DIN rail, even at 70°C ambient temperature. 
  • Units can be supplied separately or installed on PR 9400 power rail.
  • The narrow 6.1 mm housing allows up to 163 units per meter.

Data sheet & Manuals


Data sheet

Manuals

Manuals in Russian

Approvals & Certificates


ATEX certificate

IECEx certificate

UKEX certificate

UL certificate

CCC certificate

Supplementary documentation


EU Declaration of Conformity

UKCA Declaration of Conformity

EMC data

PR default configurations

Safety note


Safety note

Environmental Conditions

Operating temperature -25°C to +70°C
Storage temperature -40°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 113 x 6.1 x 115 mm
Weight approx. 70 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.5 mm2 / AWG 26...12 stranded wire
Screw terminal torque 0.5 Nm

Common specifications

Supply

Supply voltage 16.8...31.2 VDC
Fuse 400 mA SB / 250 VAC
Max. required power ≤ 1.2 W
Max. power dissipation 0.65 W

Isolation voltage

Isolation voltage, test / working 2.5 kVAC / 300 VAC (reinforced)

Response time

Response time (0...90%, 100...10%) ≤ 30 ms

Auxiliary supplies

Sensor supply limitation 23 mA, 5…17 V
Signal dynamics, output 18 bit
Long term stability, current, 1yr / 5yr @ 25°C ≤ 0.058% / ≤ 0.101%
Long term stability, voltage, 1yr / 5yr @ 25°C ≤ 0.032% / ≤ 0.058%
Accuracy See manual for details
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

Frequency input

Frequency range 0.001 Hz to 100 kHz
Time range, time function 10 μs to 999.9 s
Max. frequency / min. pulse width, with input filter ON 75 Hz / 8 ms

Sensor specifications

Tacho, trig-level LOW / HIGH ≤ -50 mV / ≥ +50 mV
NPN / PNP, trig-level LOW / HIGH ≤ 4.0 V / ≥ 7.0 V
TTL, trig-level LOW / HIGH ≤ 0.8 V / ≥ 2.0 V
S0, trig-level LOW / HIGH ≤ 2.2 mA / ≥ 9.0 mA
NAMUR, trig-level LOW / HIGH ≤ 1.2 / ≥ 2.1 mA

Special voltage / current input

User-programmable trig-levels -0.05...6.50 V 0.0...10.0 mA

Output specifications

Current output

Signal range, active 0...23 mA
Programmable signal ranges 0 / 4...20 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.001% of span / 100 Ω
Response time, programmable 0.0...60.0 s
Sensor error indication 0 / 3.5 / 23 mA / none
Current limit ≤ 28 mA

Voltage output

Signal range ≤ 11.5 VDC
Programmable signal ranges 0...1; 0…5; 0...10; 0.2...1; 2…10 VDC
Load (@ voltage output) ≥ 10 kΩ
Response time, programmable 0.0...60.0 s

Relay output

Relay functions Setpoint, Window and Latch
Hysteresis 0...100%
ON and OFF delay 0...3600 s
Power On delay 0...9999 s
Sensor error reaction Break / Make / Hold
Max. voltage 250 VAC / 200 VDC
Max. current 2 A
Max. AC power 500 VA
Max. DC current, resistive load ≤ 30 VDC 2 ADC
Max. DC current, resistive load > 30 VDC See manual for details

Observed authority requirements

EMC 2014/30/EU & UK SI 2016/1091
LVD 2014/35/EU & UK SI 2016/1101
RoHS 2011/65/EU & UK SI 2012/3032
ATEX 2014/34/EU & UK SI 2016/1107

Approvals

ATEX KEMA 10ATEX0147 X
IECEx KEM 10.0068X
UKEX DEKRA 21UKEX0055X
c UL us, UL 61010-1 E314307
CCC 2020322310003554

 

Need support to select the right product for your application?

Our sales engineers are ready to help specify the right device to meet your needs.

 

Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.

 

You can expect to get a confirmed delivery date via email within 2 days after we have received your order.

 

As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.

 

State-of-the-art manufacturing

State-of-the-art manufacturing

Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down.

 

Dedicated Presales / Aftersales

Dedicated Presale / Aftersales
Our more than 80 dedicated sales engineers can help specify the right device for your application. Backed by our 9 subsidiaries and more than 40 dedicated partners, we are directly accessible in more than 40 countries around the world.

 

Find a PR location close to you

 

Product reliability

Product reliability
Although we’d always like to be top of mind, we recognize our job is mainly to provide peace of mind. Install & Forget® is our way of saying that once installed, our devices will continue to perform even in the toughest environments. And we are not afraid to back that statement up with commitments.

 

Product deployment

Product deployment
Our devices are intuitive and simple to configure. Once installed they visualize rich diagnostics data, allowing the operator to plan preventative maintenance, maximizing process up-time.

 

 

Smart products

Smart products
Many of our devices are designed to accommodate current and future communication enablers, providing the operator with multifunctional capabilities that extends into the future.

 

Check out our range of communication interfaces

 

Smart products

 

Your request has been sent successfully. 0 items on your list
Your contact information

Company information

Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country

Your information

Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please read and agree with PR electronics’ Privacy Policy.
Get an answer within 24 hours
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

A mistake has occurred. Please call us instead

You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.
Service Red

If you need support, you are always welcome to contact us

Service Red
Newsletter Icon Red

Register here to receive our newsletter

Newsletter Icon Red