6185
Data sheet & Manuals
Data sheet
- 6185.pdf
- Latest version
Manuals
- 6185V101_UK.pdf
- 6185V100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 6185V101_RU.pdf
- 6185V100_RU.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 6185DoC_EU_102_UK.pdf
- 6185DoC_EU_101_UK.pdf
- 6185DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 6185DoC_UKCA_100_UK.pdf
- Latest version
Safety note
Safety note
- SN6185_103_2443.pdf
- SN6185_102_1933.pdf
- SN6185_101_1615.pdf
- SN6100_100_1035.pdf
- Previous versions
- Latest version
Approvals & Certificates
EAC declaration
- EAC-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Weight approx. | 155 / 180 / 230 g (1 / 2 / 4 channels) |
DIN rail type | DIN 46277 |
Wire size | 1 x 2.5 mm2 stranded wire |
Screw terminal torque | 0.5 Nm |
Common specifications
Supply |
|
Power dissipation, per channel | 40 mW |
Isolation voltage |
|
Test voltage | 2 kVAC |
Response time |
|
Response time (0...90%, 100...10%) | < 4 ms |
Voltage drop |
< 1.8 VDC, min.
1.8 V + (Iout.*Rload), max. |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of span |
Input specifications
Current input |
|
Measurement range | 0...23 mA |
Input resistance | ≈ 90 Ω + Rload (@ 20 mA) |
Output specifications
Current output |
|
Signal range | 0...23 mA |
Min. signal range | 1:1 |
Load (@ current output) | ≤ 600 Ω |
Load stability | < 0.03% of span / 100 Ω |
Current limit | 50 mA |
Voltage limit | 15 VDC |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |