Universal converter

 

9116A

 

  • Input for RTD, TC, Ohm, potentiometer, mA and V
  • Supply for 2-wire transmitters
  • Active / passive mA output and relay output
  • Can be supplied separately or installed on power rail, PR type 9400
  • SIL 2-certified via Full Assessment
Zone2 Ex Iec Iecex Zone2 Fmapprovedcus Zone2 Inmetro Dekra UL List CCC Kcs Mark SIL 2 DNV Classnk Eac Ex Mpa EAC UKCA CE Pr Rohs3
  1. Overview + -

  2. Technical details + -

  3. Accessories + -

  4. Order and delivery + -

  5. Why choose PR + -

Advanced features

  • Configuration and monitoring by way of detachable display front (PR 4500 series); process calibration, signal and relay simulation.
  • Advanced relay configuration, e.g. setpoint, window, delay, sensor error indication and power monitoring.
  • Copying of the configuration from one device to others of the same type via the display front.
  • TC inputs with internal CJC or external CJC for higher accuracy.
  • Active / passive mA output via the same two terminals.

Application

  • 9116A can be mounted in the safe area or in zone 2 / Class I, Division 2, Groups A, B, C, D.
  • Conversion and scaling of temperature, voltage, potentiometer and linear resistance signals.
  • Power supply and signal isolator for 2-wire transmitters.
  • Monitoring of error events and cable breakage via the individual status relay and/or a collective electronic signal via the power rail.
  • 9116A has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
  • Suitable for the use in systems up to Performance Level “d” according to ISO-13849.

Technical characteristics

  • 1 green and 1 red front LED indicate operation status and malfunction. 1 yellow LED indicates relay status.
  • 2.6 kVAC galvanic isolation between input, output and supply.

Mounting

  • The devices can be mounted vertically or horizontally without distance between neighbouring units.

Approvals & Certificates


ATEX certificate

IECEx certificate

UKEX certificate

FM certificate

INMETRO certificate

CCC certificate

KCs certificate

UL certificate

SIL certificate

DNV marine certificate

ClassNK certificate

EAC declaration

EAC LVD declaration

EAC Ex certificate

Metrology Pattern Approval (MPA), Russia

Supplementary documentation


EU Declaration of Conformity

UKCA Declaration of Conformity

Modbus configuration manual

EMC data

Assessment report

FMEDA report

PR default configurations

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ PR 4500 109 x 23.5 x 131 mm
Weight approx. 185 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Stripping length 5 mm
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage 19.2...31.2 VDC
Fuse 1.25 A SB / 250 VAC
Max. required power ≤ 2.1 W
Max. power dissipation ≤ 1.7 W

Isolation voltage

Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply 2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation

Response time

Temperature input, programmable (0...90%, 100...10%) 1...60 s
mA / V input (programmable) 0.4...60 s

Auxiliary supplies

9116x1x: 2-w. sup. (term. 54...52) 28...16.5 VDC / 0...20 mA
9116x2x: 2-w. sup. (term. 54...52) 21.4...16.5 VDC / 0...20 mA
Programming PR 4500 communication interfaces
Signal dynamics, input 24 bit
Signal dynamics, output 16 bit
Signal / noise ratio Min. 60 dB (0...100 kHz)
Accuracy Better than 0.1% of sel. range

Input specifications

RTD input

RTD type Pt10/20/50/100/200/250; Pt300/Pt400/500/1000; Ni50/100/120/1000
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Programmable ON / OFF
Short circuit detection Yes

Potentiometer input

Potentiometer min....max. 10 Ω...10 kΩ

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in 5910 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C
CJC via int. mounted sensor ±(2.0°C + 0.4°C * Δt)
Sensor error detection Programmable ON or OFF (only wire breakage)

Current input

Measurement range 0...23 mA
Programmable measurement ranges 0...20 and 4...20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω
Sensor error detection Loop break 4...20 mA

Voltage input

Measurement range 0...12 VDC
Programmable measurement ranges 0/0.2...1, 0/1...5, 0/2...10 VDC
Input resistance Nom. >10 MΩ

Output specifications

Current output

Signal range 0...23 mA
Programmable signal ranges 0...20/4...20/20...0/20...4 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Current limit ≤ 28 mA

Passive 2-wire mA output

Max. external 2-wire supply 26 VDC
Effect of external 2-wire supply voltage variation < 0.005% of span / V

Relay output

Relay functions Setpoint, Window, Sensor error, Power and Off
Max. voltage 250 VAC / VDC
Max. current 2 A
Max. AC power 500 VA
Max. DC current, resistive load > 30 VDC See manual for details

Status relay

Max. voltage 125 VAC / 110 VDC
Max. current 0.5 AAC / 0.3 ADC
Max. AC power 62.5 VA / 32 W

Observed authority requirements

EMC 2014/30/EU & UK SI 2016/1091
LVD 2014/35/EU & UK SI 2016/1101
RoHS 2011/65/EU & UK SI 2012/3032
ATEX 2014/34/EU & UK SI 2016/1107
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011
EAC LVD TR-CU 004/2011

Approvals

ATEX KEMA 10ATEX0053 X
IECEx KEM 10.0022X
UKEX DEKRA 21UKEX0177X
c FM us FM19US0058X / FM19CA0031X
INMETRO DEKRA 23.0006X
c UL us, UL 61010-1 E314307
c UL us, UL 913 E233311 (only 9116xx-U9)
CCC
KCs 21_AV4BO_0178X (only 9116Ax-KCs)
EAC Ex EAEU KZ 7500361.01.01.08756
DNV Marine TAA00000JD
ClassNK TA24034M
SIL SIL 2 certified & fully assessed acc. to IEC 61508

 

Need support to select the right product for your application?

Our sales engineers are ready to help specify the right device to meet your needs.

 

Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.

 

You can expect to get a confirmed delivery date via email within 2 days after we have received your order.

 

As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.

 

State-of-the-art manufacturing

State-of-the-art manufacturing

Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down.

 

Dedicated Presales / Aftersales

Dedicated Presale / Aftersales
Our more than 80 dedicated sales engineers can help specify the right device for your application. Backed by our 9 subsidiaries and more than 40 dedicated partners, we are directly accessible in more than 40 countries around the world.

 

Find a PR location close to you

 

Product reliability

Product reliability
Although we’d always like to be top of mind, we recognize our job is mainly to provide peace of mind. Install & Forget® is our way of saying that once installed, our devices will continue to perform even in the toughest environments. And we are not afraid to back that statement up with commitments.

 

Product deployment

Product deployment
Our devices are intuitive and simple to configure. Once installed they visualize rich diagnostics data, allowing the operator to plan preventative maintenance, maximizing process up-time.

 

 

Smart products

Smart products
Many of our devices are designed to accommodate current and future communication enablers, providing the operator with multifunctional capabilities that extends into the future.

 

Check out our range of communication interfaces

 

Smart products

 

Your request has been sent successfully. 0 items on your list
Your contact information

Company information

Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country

Your information

Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please read and agree with PR electronics’ Privacy Policy.
Get an answer within 24 hours
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

A mistake has occurred. Please call us instead

You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.
Service Red

If you need support, you are always welcome to contact us

Service Red
Newsletter Icon Red

Register here to receive our newsletter

Newsletter Icon Red