2914
Data sheet & Manuals
Data sheet
- 2914.pdf
- Latest version
Manuals
- 2914V102_UK.pdf
- 2914V101.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 2914DoC_EU_101_UK.pdf
- 2914DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 2229DoC_UKCA_100_UK.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
- SN2914_103_2311.pdf
- SN2914_102_1945.pdf
- SN2914_101_1615.pdf
- SN2914_3532_1035.pdf
- Previous versions
- Latest version
Approvals & Certificates
EAC declaration
- EAC-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Environmental Conditions
Operating temperature | 0°C to +70°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP30 |
Mechanical specifications
Dimensions (HxWxD) | 70 x 121 x 25 mm |
Weight approx. | 95 g |
Wire size | 1 x 1.5 mm |
Common specifications
Supply |
|
Supply voltage | 8.0...35 VDC |
Internal power dissipation | 25 mW…0.8 W |
Response time |
|
Response time | 10 s (@ 0.5 m/s) |
Voltage drop | 8.0 VDC |
Warm-up time | 5 min. |
Signal / noise ratio | Min. 60 dB |
Accuracy | Better than 0.3°C |
Signal dynamics, input | 17 bit |
Signal dynamics, output | 16 bit |
Effect of supply voltage change | < 0.005% of span / VDC |
Temperature coefficient | < ±0.01% of span / °C |
Linearity error | < 0.1% of span |
EMC immunity influence | < ±0.5% |
Input specifications
Common input specifications |
|
Max. offset | 50% of max.°C |
RTD input |
|
Sensor current | > 0.2 mA, < 0.4 mA |
Measurement range | 0...70°C |
Min. measurement range | 25°C (span) |
Output specifications
Current output |
|
Signal range | 4…20 mA |
Min. signal range | 16 mA |
Load (@ current output) | ≤ (Vsupply - 8) / 0.023 [Ω] |
Load stability | ≤ 0.01% of span / 100 Ω |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Common output specifications |
|
Updating time | 135 ms |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |