6335D
Data sheet & Manuals
Safety note
Safety note
Approvals & Certificates
CSA certificate
- 533x_633x_CSA.pdf
- Latest version
FM certificate
- 53xx_633x_FM17US0013X.pdf
- 53xx_633x_FM_2D5A7.pdf
- Previous versions
- Latest version
INMETRO certificate
- INMETRO_5335_5337_6335_6337_230011X_issue0.pdf
- Latest version
EAC declaration
- EAC_EMC_declaration_Ex_3000_5000_6000_9000.pdf
- Latest version
EAC Ex certificate
- EAC_Ex.pdf
- Latest version
Metrology Pattern Approval (MPA), Belarus
- MPA_Belarus.pdf
- Latest version
Metrology Pattern Approval (MPA), Kazakhstan
- MPA_Kazakhstan.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
CCC statement
- 5000_6000_series_CCC_statement.pdf
- Latest version
FMEDA report
- FMEDA_6335_R026V3R2.pdf
- Latest version
SIL declaration
- 5335_6335_5337_6337_7501_SIL1_declaration_Potmeter_V2.pdf
- 5335_6335_5337_6337_7501_SIL2_declaration_V2.pdf
PR default configurations
- PR_default_configurations.pdf
- Latest version
Environmental Conditions
Operating temperature | -40°C to +85°C |
Storage temperature | -40°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Weight (1 / 2 channels) | 145 / 185 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Common specifications
Supply |
|
Supply voltage | 8.0...30 VDC |
Internal power dissipation, 1 / 2 ch. | 19 mW...0.7 / 1.4 W |
Isolation voltage |
|
Isolation voltage, test / working | 1.5 kVAC / 50 VAC |
Response time |
|
Response time (programmable) | 1...60 s |
Voltage drop | 8.0 VDC |
Warm-up time | 30 s |
Programming | Loop Link & HART |
Signal / noise ratio | Min. 60 dB |
Accuracy | Better than 0.05% of selected range |
Signal dynamics, input | 22 bit |
Signal dynamics, output | 16 bit |
Effect of supply voltage change | < 0.005% of span / VDC |
Input specifications
Common input specifications |
|
Max. offset | 50% of selected max. value |
RTD input |
|
RTD type | Pt100, Ni100, lin. R |
Cable resistance per wire | 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Linear resistance input |
|
Linear resistance min....max. | 0 Ω...7000 Ω |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5 |
Cold junction compensation (CJC) | < ±1.0°C |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 33 μA / 0 μA |
Voltage input |
|
Measurement range | -800...+800 mV |
Min. measurement range (span) | 2.5 mV |
Input resistance | 10 MΩ |
Output specifications
Current output |
|
Signal range | 4…20 mA |
Min. signal range | 16 mA |
Load (@ current output) | ≤ (Vsupply - 8) / 0.023 [Ω] |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | Programmable 3.5…23 mA |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Common output specifications |
|
Updating time | 440 ms |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals
ATEX | DEKRA 20ATEX0108X |
IECEx | DEK 20.0063X |
CSA | 1125003 |
FM | FM17US0013X |
INMETRO | DEKRA 23.0011X |
EAC Ex | RU C-DK.HA65.B.00355/19 |
SIL | Hardware assessed for use in SIL applications |