Trip amplifier
2231
- AC/DC trip amplifier
- 2 adjustable alarm limits
- Galvanically isolated 3.75 kVAC
- Front-programmable
- 3-digit LED display
- 24 VDC or universal supply
Advanced features
- The front-operated push buttons are used for programming the different standard functions.
- A password can prevent access for changing parameters.
Application
- Alarm detector in connection with measurement of AC/DC current or voltage signals.
- The unit is used where accurate setpoint setting and different alarm functions are required.
- The unit can be used as a single or dual trip amplifier.
- Used in applications where programmable parameters such as hysteresis, setpoint, reset, active relay for increasing or decreasing signal, delay and input signal need to be set.
Technical characteristics
- 3-digit display showing the input signal in %.
- Two LED indicating relay status.
- 3 pushbuttons for programming.
- Standard DC current input signals in the range 0...20 mA.
- DC voltage signals in the range 0...250 VDC.
- AC current signals up to 1 A.
- True RMS measurement of AC voltage signals in the range 0...250 VAC.
- Mounting for a standard 11-pole socket which can be adapted for DIN rail or plate use with PR’s 7023 adaptor and 7024 mounting keying.
Ficha técnica y manuales
Ficha técnica
- 2231.pdf
- Última versión
Manuales
- 2231V106_UK.pdf
- 2231V105_UK.pdf
- 2231V104_UK.pdf
- Versiones anteriores
- Última versión
Manuales en ruso
- 2231V106_RU.pdf
- 2231V105_RU.pdf
- 2231V104_RU.pdf
- Versiones anteriores
- Última versión
Documentación complementaria
Declaración UE de conformidad
- 2231DoC_EU_103_UK.pdf
- 2231DoC_EU_102_UK.pdf
- 2231DoC_EU_101_UK.pdf
- 2231DoC_EU_100_UK.pdf
- Versiones anteriores
- Última versión
Configuraciones por defecto
- PR_default_configurations.pdf
- Última versión
Nota de seguridad
Nota de seguridad
- SN2200-1_107_2436.pdf
- SN2200-1_106_2340.pdf
- SN2200-1_105_2232.pdf
- SN2200-1_104_1937.pdf
- SN2200-1_103_1745.pdf
- SN2200-1_102_1613.pdf
- SN2200-1_100_1106.pdf
- Versiones anteriores
- Última versión
Homologaciones y certificados
Certificado marina DNV
- DNV_2231_41xx_51xx_53xx.pdf
- Última versión
Declaración EAC
- EAC-Declaration.pdf
- Última versión
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Última versión
Formulario de pedido
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP50 |
Mechanical specifications
Dimensions (HxWxD) | 80.5 x 35.5 x 84.5 mm (D is without pins) |
Weight DC / universally supplied | 125 g / 175 g |
Common specifications
Supply |
|
Supply voltage | 19.2...28.8 VDC |
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Internal power dissipation |
1.5 W (2231D)
2 W (2231P) |
Isolation voltage |
|
Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
PELV/SELV | IEC 61140 |
Response time |
|
Response time (programmable) |
0.25...60 s (DC)
0.75...60 s (AC) |
Updating time | 100 ms |
Accuracy | Better than 0.1% of sel. range |
Signal dynamics, input | 16 bit |
Effect of supply voltage change | < ±0.002% of span / %V |
Temperature coefficient |
< ±0.01% of span /°C (DC signals)
< ±0.02% of span /°C (AC signals) |
Linearity error |
< 0.1% of span
< ±0.35% of span 50...1000 Hz (AC sine wave signals) |
EMC immunity influence | < ±0.5% |
Input specifications
Common input specifications |
|
Max. offset | 50% of selected max. value |
Current input |
|
Measurement range | 0...20 mA |
Min. measurement range (span) | 10 mA |
Input resistance | 50 Ω |
AC current input |
|
Measurement range | 0...1 ARMS |
Min. measurement range (span) | 0.5 ARMS |
Input resistance | 1 Ω / 2 W |
Voltage input |
|
Measurement range | 0...250 VDC |
Min. measurement range (span) | 0.5 VDC |
Input resistance | Nom. 5 MΩ |
AC voltage input |
|
AC voltage input | 0...250 VRMS |
Min. measurement range (span) | 0.5 VRMS |
Input resistance | Nom. 5 MΩ |
Output specifications
Relay output |
|
Hysteresis | 0...99.9% of span |
ON and OFF delay | 0.0...99.9 s |
Max. voltage | 250 VAC / VDC |
Max. current | 2 A |
Max. AC power | 500 VA |
Max. DC current, resistive load ≤ 30 VDC | 2 ADC |
Max. DC current, resistive load > 30 VDC | See manual for details |
Common output specifications |
|
Updating time | 100 ms |
Relay outputs: Setpoint setting | 0...99.9% of span |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
RoHS | 2011/65/EU |
EAC | TR-CU 020/2011 |
Approvals
DNV Marine | TAA0000101 |
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.
You can expect to get a confirmed delivery date via email within 2 days after we have received your order.
As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
Dedicated Presale / Aftersales
|
Product reliability |
Product deployment
|
Smart products
Check out our range of communication interfaces
|