Programmable LED indicator
5714
- 4-digit 14-segment LED display
- Input for mA, V, Ohm, RTD, TC and potentiometer
- 2 relays and analog output
- Universal supply
- Front key programmable
Application
- Display for digital readout of current / voltage / resistance / temperature or potentiometer signals.
- Process control with 2 potential-free relays and / or analog output.
- For local readout in extremely wet atmospheres with a specially designed splash-proof cover.
Technical characteristics
- 4-digit LED indicator with 13.8 mm 14-segment characters. Max. display readout -1999...9999 with programmable decimal point and relay ON / OFF indication.
- All standard operational parameters can be adjusted to any application by way of the front function keys.
- Help texts in eight languages can be selected via a menu item.
- PR 5714 is available fully-configured according to specifications ready for process control and visualization.
- 2.3 kVAC galvanic isolation between input, output and supply.
- In versions with relay outputs the user can minimize the installation test time by activating / deactivating each relay independently of the input signal.
Mounting / installation
- To be mounted in panel front. The included rubber packing must be mounted between the panel cutout hole and the display front to obtain a protection degree of IP65 (type 4X). For extra protection in extreme environments, PR5714 can be delivered with a specially designed splash-proof cover as accessory.
Data sheet & Manuals
Safety note
Safety note
- SN5500_5700_107_2418.pdf
- SN5500_5700_106_2208.pdf
- SN5500_5700_105_2050.pdf
- SN5500_5700_104_1613.pdf
- SN5500_5700_103_1304.pdf
- Previous versions
- Latest version
Approvals & Certificates
UL certificate
- 5714-15-25_UL.pdf
- Latest version
DNV EU-RO marine certificate
- DNV_EU_RO_4114_4116_4131_5714_5715_5725.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
EAC LVD declaration
- EAC_LVD-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
Order form
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree (mounted in panel) | IP65 / Type 4X |
Mechanical specifications
Dimensions (HxWxD) | 48 x 96 x 120 mm |
Cut out dimensions | 44.5 x 91.5 mm |
Weight approx. | 230 g |
Wire size, pin 41-46 (max.) | 0.05...1.31 mm2 AWG 30...16 stranded wire |
Wire size, others, max. | 0.05...3.31 mm2 / AWG 30...12 stranded wire |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Max. required power |
2.5 W (5714A)
3.0 W (5714B/C) 3.5 W (5714D) |
Internal power dissipation |
2.2 W (5714A)
2.7 W (5714B/C) 3.2 W (5714D) |
Isolation voltage |
|
Isolation voltage, test / working | 2.3 kVAC / 250 VAC |
Response time |
|
Temperature input, programmable (0...90%, 100...10%) | 1...60 s |
mA / V input (programmable) | 0.4...60 s |
Auxiliary supplies |
|
2-wire supply (pin 46...45) | > 15 VDC @ 0...20 mA |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of readout |
Input specifications
RTD input |
|
RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
Cable resistance per wire | 50 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Linear resistance input |
|
Linear resistance min....max. | 0 Ω...10000 Ω |
Potentiometer input |
|
Potentiometer min....max. | 10 Ω...100 kΩ |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input |
|
Measurement range | 0...23 mA |
Programmable measurement ranges | 0...20 and 4...20 mA |
Input resistance | Nom. 20 Ω + PTC 25 Ω |
Sensor error detection | Loop break 4...20 mA |
Voltage input |
|
Measurement range | 0...12 VDC |
Programmable measurement ranges | 0/0.2...1; 0/2...10 VDC |
Input resistance | Nom. 10 MΩ |
Output specifications
Display |
|
Display readout | -1999...9999 (4 digits) |
Decimal point | Programmable |
Digit height | 13.8 mm |
Display updating. | 2.2 times / s |
Input outside input range is indicated by | Explanatory text |
Current output |
|
Signal range | 0...23 mA |
Programmable signal ranges | 0...20/4...20/20...0/20...4 mA |
Load (@ current output) | ≤ 800 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | 0 / 3.5 / 23 mA / none |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Output limitation, on 4...20 and 20...4 mA signals | 3.8...20.5 mA |
Output limitation, on 0...20 and 20...0 mA signals | 0...20.5 mA |
Current limit | ≤ 28 mA |
Relay output |
|
Relay functions | Setpoint |
Hysteresis | 0...100% |
ON and OFF delay | 0...3600 s |
Sensor error reaction | Break / Make / Hold |
Max. voltage | 250 VAC / VDC |
Max. current | 2 A |
Max. AC power | 500 VA |
Max. DC current, resistive load > 30 VDC | See manual for details |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC LVD | TR-CU 004/2011 |
Approvals
c UL us, UL 508 | E248256 |
EU RO MR Type Approval | MRA000000Z |
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.
You can expect to get a confirmed delivery date via email within 2 days after we have received your order.
As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
Dedicated Presale / Aftersales
|
Product reliability |
Product deployment
|
Smart products
Check out our range of communication interfaces
|