4511
Data sheet & Manuals
Data sheet
- 4511.pdf
- Latest version
Manuals
- 4511V104_UK.pdf
- 4511V103_UK.pdf
- 4511V102_UK.pdf
- 4511V101_UK.pdf
- 4511V100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 4511V104_RU.pdf
- 4511V103_RU.pdf
- 4511V102_RU.pdf
- 4511V101_RU.pdf
- 4511V100_RU.pdf
- Previous versions
- Latest version
Approvals & Certificates
ATEX certificate
- 4511_issue4.pdf
- Latest version
IECEx certificate
- 4511IEC_issue3.pdf
- Latest version
UKEX certificate
- 4511UKEX_Issue 0.pdf
- Latest version
FM certificate
UL certificate
- 4511_UL.pdf
- Latest version
DNV marine certificate
- DNV_9xxx_4510_4511.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 4511DoC_EU_104_UK.pdf
- 4511DoC_EU_103_UK.pdf
- 4511DoC_EU_102_UK.pdf
- 4511DoC_EU_101_UK.pdf
- 4511DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 4511DoC_UKCA_100_UK.pdf
- Latest version
Safety note
Safety note
- SN4500_106_2443.pdf
- SN4500_105_2239.pdf
- SN4511_104_2124.pdf
- SN4511_102_1811.pdf
- SN4511_101_1613.pdf
- SN4511_100_1350.pdf
- Previous versions
- Latest version
Environmental Conditions
Operating temperature | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 73.2 x 23.3 x 26.5 mm |
Dimensions (HxWxD) w/ 4000/9000 unit | 109 x 23.5 x 131 mm |
Weight approx. | 30 g |
Connection | RJ45 - shielded |
Common specifications
Supply |
|
Max. required power | 0.15 W |
Isolation voltage |
|
Isolation voltage, test / working | 2.5 kVAC / 250 VAC reinforced isolation |
Response time |
|
Response time | < 20 ms |
Signal / noise ratio | > 60 dB |
Update rate | > 50 Hz |
Extended EMC immunity: NAMUR NE21, A criterion, burst | No loss of communication |
Signal type | RS-485 half duplex |
Serial protocol | Modbus RTU |
Modbus mode | RTU - slave |
Devices on an RS485 line | Up to 32 (w/o a repeater) |
Data rates, baud | 2400, 4800, 9600, 19200, 38400, 57600, 115200 |
Automatic baudrate detection | Yes - can be configured ON or OFF |
Parity | Even, Odd, None |
Stop bit(s) | 1 or 2 |
Digital addressing | 1...247 |
Response delay | 0...1000 ms |
I.S. / Ex marking
ATEX | II 3 G Ex ec IIC T5 |
IECEx | Ex ec IIC T5 Gc |
FM, US | Cl I, Div 2, Gp A, B, C, D T5; Cl I, Zn 2, AEx ec IIC T5 Gc |
FM, CA | Cl I, Div 2, Gp A, B, C, D T5; Ex ec IIC T5 Gc |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
Approvals
ATEX | DEKRA 13ATEX0098 X |
IECEx | DEK 13.0026 X |
c FM us | FM22US0014X / FM22CA0009X |
UKEX | DEKRA 21UKEX0167X |
c UL us, UL 61010-1 | E314307 |
DNV Marine | TAA00000JD |