5714
Data sheet & Manuals
Data sheet
- 5714.pdf
- Latest version
Manuals
- 5714V105_UK.pdf
- 5714V104_UK.pdf
- 5714V103_UK.pdf
- 5714V102.pdf
- 5714V101.pdf
- 5714V100.pdf
- Previous versions
- Latest version
Manuals in Russian
- 5714V105_RU.pdf
- 5714V104_RU.pdf
- 5714V103_RU.pdf
- 5714L102_RU.pdf
- 5714L101_RU.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 5714DoC_EU_103_UK.pdf
- 5714DoC_EU_102_UK.pdf
- 5714DoC_EU_101_UK.pdf
- 5714DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 5714DoC_UKCA_100_UK.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
- SN5500_5700_107_2418.pdf
- SN5500_5700_106_2208.pdf
- SN5500_5700_105_2050.pdf
- SN5500_5700_104_1613.pdf
- SN5500_5700_103_1304.pdf
- Previous versions
- Latest version
Approvals & Certificates
UL certificate
- 5714-15-25_UL.pdf
- Latest version
DNV EU-RO marine certificate
- DNV_EU_RO_4114_4116_4131_5714_5715_5725.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
EAC LVD declaration
- EAC_LVD-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree (mounted in panel) | IP65 / Type 4X |
Mechanical specifications
Dimensions (HxWxD) | 48 x 96 x 120 mm |
Cut out dimensions | 44.5 x 91.5 mm |
Weight approx. | 230 g |
Wire size, pin 41-46 (max.) | 0.05...1.31 mm2 AWG 30...16 stranded wire |
Wire size, others, max. | 0.05...3.31 mm2 / AWG 30...12 stranded wire |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Max. required power |
2.5 W (5714A)
3.0 W (5714B/C) 3.5 W (5714D) |
Internal power dissipation |
2.2 W (5714A)
2.7 W (5714B/C) 3.2 W (5714D) |
Isolation voltage |
|
Isolation voltage, test / working | 2.3 kVAC / 250 VAC |
Response time |
|
Temperature input, programmable (0...90%, 100...10%) | 1...60 s |
mA / V input (programmable) | 0.4...60 s |
Auxiliary supplies |
|
2-wire supply (pin 46...45) | > 15 VDC @ 0...20 mA |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of readout |
Input specifications
RTD input |
|
RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
Cable resistance per wire | 50 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Linear resistance input |
|
Linear resistance min....max. | 0 Ω...10000 Ω |
Potentiometer input |
|
Potentiometer min....max. | 10 Ω...100 kΩ |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input |
|
Measurement range | 0...23 mA |
Programmable measurement ranges | 0...20 and 4...20 mA |
Input resistance | Nom. 20 Ω + PTC 25 Ω |
Sensor error detection | Loop break 4...20 mA |
Voltage input |
|
Measurement range | 0...12 VDC |
Programmable measurement ranges | 0/0.2...1; 0/2...10 VDC |
Input resistance | Nom. 10 MΩ |
Output specifications
Display |
|
Display readout | -1999...9999 (4 digits) |
Decimal point | Programmable |
Digit height | 13.8 mm |
Display updating. | 2.2 times / s |
Input outside input range is indicated by | Explanatory text |
Current output |
|
Signal range | 0...23 mA |
Programmable signal ranges | 0...20/4...20/20...0/20...4 mA |
Load (@ current output) | ≤ 800 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | 0 / 3.5 / 23 mA / none |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Output limitation, on 4...20 and 20...4 mA signals | 3.8...20.5 mA |
Output limitation, on 0...20 and 20...0 mA signals | 0...20.5 mA |
Current limit | ≤ 28 mA |
Relay output |
|
Relay functions | Setpoint |
Hysteresis | 0...100% |
ON and OFF delay | 0...3600 s |
Sensor error reaction | Break / Make / Hold |
Max. voltage | 250 VAC / VDC |
Max. current | 2 A |
Max. AC power | 500 VA |
Max. DC current, resistive load > 30 VDC | See manual for details |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC LVD | TR-CU 004/2011 |
Approvals
c UL us, UL 508 | E248256 |
EU RO MR Type Approval | MRA000000Z |