2231
Data sheet & Manuals
Data sheet
- 2231.pdf
- Latest version
Manuals
- 2231V106_UK.pdf
- 2231V105_UK.pdf
- 2231V104_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 2231V106_RU.pdf
- 2231V105_RU.pdf
- 2231V104_RU.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 2231DoC_EU_103_UK.pdf
- 2231DoC_EU_102_UK.pdf
- 2231DoC_EU_101_UK.pdf
- 2231DoC_EU_100_UK.pdf
- Previous versions
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Safety note
Safety note
- SN2200-1_107_2436.pdf
- SN2200-1_106_2340.pdf
- SN2200-1_105_2232.pdf
- SN2200-1_104_1937.pdf
- SN2200-1_103_1745.pdf
- SN2200-1_102_1613.pdf
- SN2200-1_100_1106.pdf
- Previous versions
- Latest version
Approvals & Certificates
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP50 |
Mechanical specifications
Dimensions (HxWxD) | 80.5 x 35.5 x 84.5 mm (D is without pins) |
Weight DC / universally supplied | 125 g / 175 g |
Common specifications
Supply |
|
Supply voltage | 19.2...28.8 VDC |
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Internal power dissipation |
1.5 W (2231D)
2 W (2231P) |
Isolation voltage |
|
Isolation voltage, test / working | 3.75 kVAC / 250 VAC |
PELV/SELV | IEC 61140 |
Response time |
|
Response time (programmable) |
0.25...60 s (DC)
0.75...60 s (AC) |
Updating time | 100 ms |
Accuracy | Better than 0.1% of sel. range |
Signal dynamics, input | 16 bit |
Effect of supply voltage change | < ±0.002% of span / %V |
Temperature coefficient |
< ±0.01% of span /°C (DC signals)
< ±0.02% of span /°C (AC signals) |
Linearity error |
< 0.1% of span
< ±0.35% of span 50...1000 Hz (AC sine wave signals) |
EMC immunity influence | < ±0.5% |
Input specifications
Common input specifications |
|
Max. offset | 50% of selected max. value |
Current input |
|
Measurement range | 0...20 mA |
Min. measurement range (span) | 10 mA |
Input resistance | 50 Ω |
AC current input |
|
Measurement range | 0...1 ARMS |
Min. measurement range (span) | 0.5 ARMS |
Input resistance | 1 Ω / 2 W |
Voltage input |
|
Measurement range | 0...250 VDC |
Min. measurement range (span) | 0.5 VDC |
Input resistance | Nom. 5 MΩ |
AC voltage input |
|
AC voltage input | 0...250 VRMS |
Min. measurement range (span) | 0.5 VRMS |
Input resistance | Nom. 5 MΩ |
Output specifications
Relay output |
|
Hysteresis | 0...99.9% of span |
ON and OFF delay | 0.0...99.9 s |
Max. voltage | 250 VAC / VDC |
Max. current | 2 A |
Max. AC power | 500 VA |
Max. DC current, resistive load ≤ 30 VDC | 2 ADC |
Max. DC current, resistive load > 30 VDC | See manual for details |
Common output specifications |
|
Updating time | 100 ms |
Relay outputs: Setpoint setting | 0...99.9% of span |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU |
LVD | 2014/35/EU |
RoHS | 2011/65/EU |
EAC | TR-CU 020/2011 |
Approvals
DNV Marine | TAA0000101 |