5332A
Data sheet & Manuals
Data sheet
- 5332A.pdf
- Latest version
Manuals
- 5332V105_UK.pdf
- 5332V104_UK.pdf
- 5332V103_UK.pdf
- 5332V102_UK.pdf
- 5332V101_UK.pdf
- 5332V100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 5332V105_RU.pdf
- 5332V104_RU.pdf
- 5332V103_RU.pdf
- 5332V102_RU.pdf
- 5332V101_RU.pdf
- 5332V100_RU.pdf
- Previous versions
- Latest version
Approvals & Certificates
ATEX certificate
- 5332A_20ATEX0096X_issue0.pdf
- 5332A_10ATEX0002X_issue03.pdf
- Previous versions
- Latest version
IECEx certificate
- 5332AIEC_200059X_issue0.pdf
- 5332AIEC_130035X_issue1.pdf
- Previous versions
- Latest version
EAC declaration
- EAC_EMC_declaration_Ex_3000_5000_6000_9000.pdf
- Latest version
EAC Ex certificate
- EAC_Ex.pdf
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 5332DoC_EU_106_UK.pdf
- 5332DoC_EU_105_UK.pdf
- 5332DoC_EU_104_UK.pdf
- 5332DoC_EU_103_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 5332DoC_UKCA_100_UK.pdf
- Latest version
CCC statement
- 5000_6000_series_CCC_statement.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Environmental Conditions
Operating temperature | -40°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree (encl./terminal) | IP68 / IP00 |
Mechanical specifications
Dimensions | Ø 44 x 20.2 mm |
Weight approx. | 50 g |
Wire size | 1 x 1.5 mm2 stranded wire |
Screw terminal torque | 0.4 Nm |
Common specifications
Supply |
|
Supply voltage | 7.2...35 VDC |
Internal power dissipation | 25 mW…0.8 W |
Response time |
|
Response time (programmable) | 1...60 s |
Voltage drop | 7.2 VDC |
Warm-up time | 5 min. |
Power on to stable output | 4.5 s |
Programming | Loop Link |
Signal / noise ratio | > 60 dB |
EEprom error check | < 3.5 s |
Accuracy | Better than 0.05% of selected range |
Signal dynamics, input | 20 bit |
Signal dynamics, output | 16 bit |
Effect of supply voltage change | < 0.005% of span / VDC |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Common input specifications |
|
Max. offset | 50% of selected max. value |
RTD input |
|
RTD type | Pt100, Ni100, lin. R |
Cable resistance per wire | 5 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Linear resistance input |
|
Linear resistance min....max. | 0 Ω...5000 Ω |
Output specifications
Common output specifications |
|
Updating time | 440 ms |
Current output |
|
Signal range | 4…20 mA |
Min. signal range | 16 mA |
Load (@ current output) | ≤ (Vsupply - 7.2) / 0.023 [Ω] |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | Programmable 3.5…23 mA |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
of span | = of the presently selected range |
I.S. / Ex marking
ATEX | II 3 G Ex nA [ic] IIC T6...T4 Gc, II 3 G Ex ec [ic] IIC T6...T4 Gc, II 3 G Ex ic IIC T6...T4 Gc, II 3 D Ex ic IIIC Dc |
IECEx | Ex nA [ic] IIC T6…T4 Gc, Ex ec [ic] IIC T6…T4 Gc, Ex ic IIC T6…T4 Gc, Ex ic IIIC Dc |
CSA | Cl. I, Div. 2, Gp. A, B, C, D T6...T4, Ex nA[ic] IIC T6…T4 Gc |
INMETRO | Ex ec [ic] IIC T6...T4 Gc, Ex ic IIC T6...T4 Gc, Ex ic IIIC Dc |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals
ATEX | DEKRA 20ATEX0096X |
IECEx | DEK 20.0059X |
CSA | 1125003 |
INMETRO | DEKRA 23.0009X |
EAC Ex | RU C-DK.HA65.B.00355/19 |