Universal trip amplifier

 

4131

 

  • Input for RTD, TC, Ohm, potentiometer, mA and V
  • 2 adjustable alarm limits
  • FM-approved for installation in Div. 2
  • 2 relay outputs
  • Universal AC or DC supply
UL List Fmapproved DNV Dnv Eu Ro Mpa EAC UKCA CE Pr Rohs3 Guarantee
  1. Overview + -

  2. Technical details + -

  3. Accessories + -

  4. Order and delivery + -

  5. Why choose PR + -

Advanced features

  • Programmable via detachable display front (PR 4500 series), process calibration, relay simulation, password protection, error diagnostics and selection of help text in several languages.

Application

  • Process control with 2 pairs of potential-free relay contacts which can be configured to suit any application.
  • Trip amplifier with window function defined by a high and a low setpoint. The relay changes state outside the window.
  • Relay latch function, where the relay is activated and can only be reset manually.
  • Sophisticated sensor error surveillance, where one relay holds the state immediately prior to the sensor error, while allowing the process to continue. The other relay can be set for sensor error alarm so that the defect sensor can be replaced immediately.

Technical characteristics

  • When 4131 is used with the PR 4500 display series, all operational parameters can be modified to suit any application. As the 4131 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
  • A green front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
  • Continuous check of vital stored data for safety reasons.
  • 3-port 2.3 kVAC galvanic isolation.

Data sheet & Manuals


Data sheet

Manuals

Manuals in Russian

Supplementary documentation


EU Declaration of Conformity

UKCA Declaration of Conformity

Modbus configuration manual

EMC data

PR default configurations

Approvals & Certificates


FM certificate

UL certificate

DNV marine certificate

DNV EU-RO marine certificate

EAC declaration

EAC LVD declaration

Metrology Pattern Approval (MPA), Russia

Environmental Conditions

Operating temperature -20°C to +60°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ PR 4500 109 x 23.5 x 131 mm
Weight approx. 170 g
Weight incl. 4501 / 451x (approx.) 185 g / 200 g
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC
Fuse 400 mA SB / 250 VAC
Max. required power ≤ 2.0 W
Max. power dissipation ≤ 2.0 W

Isolation voltage

Isolation voltage, test / working 2.3 kVAC / 250 VAC

Response time

Temperature input (0...90%, 100...10%) ≤ 1 s
mA / V input (0...90%, 100...10%) ≤ 400 ms

Auxiliary supplies

2-w. supply (term. 44...43) 25...16 VDC / 0...20 mA
Programming PR 4500 communication interfaces
Signal / noise ratio Min. 60 dB (0...100 kHz)
Accuracy Better than 0.1% of sel. range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

RTD input

RTD type Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes
Short circuit detection < 15 Ω

Linear resistance input

Linear resistance min....max. 0 Ω...10000 Ω

Potentiometer input

Potentiometer min....max. 10 Ω...100 kΩ

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in 5910 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C
CJC via int. mounted sensor ±(2.0°C + 0.4°C * Δt)
Sensor error detection Yes
Sensor error current: When detecting / else Nom. 2 μA / 0 μA

Current input

Measurement range 0...23 mA
Programmable measurement ranges 0...20 and 4...20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω

Voltage input

Measurement range 0...12 VDC
Programmable measurement ranges 0/0.2...1, 0/1...5, 0/2...10 VDC
Input resistance Nom. 10 MΩ

Output specifications

Relay output

Relay functions Setpoint, Window, Sensor error, Latch, Power and Off
Hysteresis 0...100%
ON and OFF delay 0...3600 s
Max. voltage 250 VRMS
Max. current 2 AAC or 1 ADC
Max. AC power 500 VA
Sensor error reaction Break / Make / Hold
of span = of the presently selected range

Observed authority requirements

EMC 2014/30/EU & UK SI 2016/1091
LVD 2014/35/EU & UK SI 2016/1101
RoHS 2011/65/EU & UK SI 2012/3032
EAC TR-CU 020/2011
EAC LVD TR-CU 004/2011

Approvals

c UL us, UL 508 E231911
FM 3025177
DNV Marine TAA0000101
EU RO MR Type Approval MRA000000Z

 

Need support to select the right product for your application?

Our sales engineers are ready to help specify the right device to meet your needs.

 

Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.

 

You can expect to get a confirmed delivery date via email within 2 days after we have received your order.

 

As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.

 

State-of-the-art manufacturing

State-of-the-art manufacturing

Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down.

 

Dedicated Presales / Aftersales

Dedicated Presale / Aftersales
Our more than 80 dedicated sales engineers can help specify the right device for your application. Backed by our 9 subsidiaries and more than 40 dedicated partners, we are directly accessible in more than 40 countries around the world.

 

Find a PR location close to you

 

Product reliability

Product reliability
Although we’d always like to be top of mind, we recognize our job is mainly to provide peace of mind. Install & Forget® is our way of saying that once installed, our devices will continue to perform even in the toughest environments. And we are not afraid to back that statement up with commitments.

 

Product deployment

Product deployment
Our devices are intuitive and simple to configure. Once installed they visualize rich diagnostics data, allowing the operator to plan preventative maintenance, maximizing process up-time.

 

 

Smart products

Smart products
Many of our devices are designed to accommodate current and future communication enablers, providing the operator with multifunctional capabilities that extends into the future.

 

Check out our range of communication interfaces

 

Smart products

 

Your request has been sent successfully. 0 items on your list
Your contact information

Company information

Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country

Your information

Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please read and agree with PR electronics’ Privacy Policy.
Get an answer within 24 hours
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

A mistake has occurred. Please call us instead

You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.
Contact us

If you need support, you are always welcome to contact us

Contact us
Newsletter Icon Red

Register here to receive our newsletter

Newsletter Icon Red