4131
Data sheet & Manuals
Data sheet
- 4131.pdf
- Latest version
Manuals
- 4131V106_UK.pdf
- 4131V105_UK.pdf
- 4131V104_UK.pdf
- 4131V103_UK.pdf
- 4131V102_UK.pdf
- 4131V101_UK.pdf
- 4131V100_UK.pdf
- Previous versions
- Latest version
Manuals in Russian
- 4131V106_RU.pdf
- 4131V105_RU.pdf
- 4131V104_RU.pdf
- 4131V103_RU.pdf
- 4131L102_RU.pdf
- Previous versions
- Latest version
Supplementary documentation
EU Declaration of Conformity
- 4131DoC_EU_103_UK.pdf
- 4131DoC_EU_102_UK.pdf
- 4131DoC_EU_101_UK.pdf
- 4131DoC_EU_100_UK.pdf
- Previous versions
- Latest version
UKCA Declaration of Conformity
- 4131DoC_UKCA_100_UK.pdf
- Latest version
Modbus configuration manual
- 4131_MCM_103.pdf
- 4131_MCM_102.pdf
- 4131_MCM_101.pdf
- 4131_MCM_100.pdf
- Previous versions
- Latest version
EMC data
- 4000_EMC_data.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Approvals & Certificates
UL certificate
- 4114_4116_4131_4222_UL.pdf
- Latest version
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
DNV EU-RO marine certificate
- DNV_EU_RO_4114_4116_4131_5714_5715_5725.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
EAC LVD declaration
- EAC_LVD-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ PR 4500 | 109 x 23.5 x 131 mm |
Weight approx. | 170 g |
Weight incl. 4501 / 451x (approx.) | 185 g / 200 g |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 2.0 W |
Max. power dissipation | ≤ 2.0 W |
Isolation voltage |
|
Isolation voltage, test / working | 2.3 kVAC / 250 VAC |
Response time |
|
Temperature input (0...90%, 100...10%) | ≤ 1 s |
mA / V input (0...90%, 100...10%) | ≤ 400 ms |
Auxiliary supplies |
|
2-w. supply (term. 44...43) | 25...16 VDC / 0...20 mA |
Programming | PR 4500 communication interfaces |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
RTD input |
|
RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
Cable resistance per wire | 50 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Short circuit detection | < 15 Ω |
Linear resistance input |
|
Linear resistance min....max. | 0 Ω...10000 Ω |
Potentiometer input |
|
Potentiometer min....max. | 10 Ω...100 kΩ |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) via ext. sensor in 5910 | 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C |
CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input |
|
Measurement range | 0...23 mA |
Programmable measurement ranges | 0...20 and 4...20 mA |
Input resistance | Nom. 20 Ω + PTC 50 Ω |
Voltage input |
|
Measurement range | 0...12 VDC |
Programmable measurement ranges | 0/0.2...1, 0/1...5, 0/2...10 VDC |
Input resistance | Nom. 10 MΩ |
Output specifications
Relay output |
|
Relay functions | Setpoint, Window, Sensor error, Latch, Power and Off |
Hysteresis | 0...100% |
ON and OFF delay | 0...3600 s |
Max. voltage | 250 VRMS |
Max. current | 2 AAC or 1 ADC |
Max. AC power | 500 VA |
Sensor error reaction | Break / Make / Hold |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC LVD | TR-CU 004/2011 |
Approvals
c UL us, UL 508 | E231911 |
FM | 3025177 |
DNV Marine | TAA0000101 |
EU RO MR Type Approval | MRA000000Z |