Universal trip amplifier
4131
- Input for RTD, TC, Ohm, potentiometer, mA and V
- 2 adjustable alarm limits
- FM-approved for installation in Div. 2
- 2 relay outputs
- Universal AC or DC supply
Advanced features
- Programmable via detachable display front (PR 4500 series), process calibration, relay simulation, password protection, error diagnostics and selection of help text in several languages.
Application
- Process control with 2 pairs of potential-free relay contacts which can be configured to suit any application.
- Trip amplifier with window function defined by a high and a low setpoint. The relay changes state outside the window.
- Relay latch function, where the relay is activated and can only be reset manually.
- Sophisticated sensor error surveillance, where one relay holds the state immediately prior to the sensor error, while allowing the process to continue. The other relay can be set for sensor error alarm so that the defect sensor can be replaced immediately.
Technical characteristics
- When 4131 is used with the PR 4500 display series, all operational parameters can be modified to suit any application. As the 4131 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
- Continuous check of vital stored data for safety reasons.
- 3-port 2.3 kVAC galvanic isolation.
Data sheet & Manuals
Safety note
Safety note
- SN4000_1_107_2420.pdf
- SN4000_1_106_2109.pdf
- SN4000_105_2001.pdf
- SN4000_104_1741.pdf
- SN4000_103_1613.pdf
- SN4000_102_1506.pdf
- Previous versions
- Latest version
Approvals & Certificates
FM certificate
- 4104_14_16_31_4222_FM.pdf
- Latest version
UL certificate
- 4114_4116_4131_4222_UL.pdf
- Latest version
DNV marine certificate
- DNV_2231_41xx_51xx_53xx.pdf
- Latest version
DNV EU-RO marine certificate
- DNV_EU_RO_4114_4116_4131_5714_5715_5725.pdf
- Latest version
EAC declaration
- EAC-Declaration.pdf
- Latest version
EAC LVD declaration
- EAC_LVD-Declaration.pdf
- Latest version
Metrology Pattern Approval (MPA), Russia
- MPA_Russia.pdf
- Latest version
Supplementary documentation
Modbus configuration manual
- 4131_MCM_103.pdf
- 4131_MCM_102.pdf
- 4131_MCM_101.pdf
- 4131_MCM_100.pdf
- Previous versions
- Latest version
EMC data
- 4000_EMC_data.pdf
- Latest version
PR default configurations
- PR_default_configurations.pdf
- Latest version
Order form
Environmental Conditions
Operating temperature | -20°C to +60°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ PR 4500 | 109 x 23.5 x 131 mm |
Weight approx. | 170 g |
Weight incl. 4501 / 451x (approx.) | 185 g / 200 g |
Wire size | 0.13...2.08 mm2 AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common specifications
Supply |
|
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 2.0 W |
Max. power dissipation | ≤ 2.0 W |
Isolation voltage |
|
Isolation voltage, test / working | 2.3 kVAC / 250 VAC |
Response time |
|
Temperature input (0...90%, 100...10%) | ≤ 1 s |
mA / V input (0...90%, 100...10%) | ≤ 400 ms |
Auxiliary supplies |
|
2-w. supply (term. 44...43) | 25...16 VDC / 0...20 mA |
Programming | PR 4500 communication interfaces |
Signal / noise ratio | Min. 60 dB (0...100 kHz) |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
RTD input |
|
RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
Cable resistance per wire | 50 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Short circuit detection | < 15 Ω |
Linear resistance input |
|
Linear resistance min....max. | 0 Ω...10000 Ω |
Potentiometer input |
|
Potentiometer min....max. | 10 Ω...100 kΩ |
TC input |
|
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) via ext. sensor in 5910 | 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C |
CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Current input |
|
Measurement range | 0...23 mA |
Programmable measurement ranges | 0...20 and 4...20 mA |
Input resistance | Nom. 20 Ω + PTC 50 Ω |
Voltage input |
|
Measurement range | 0...12 VDC |
Programmable measurement ranges | 0/0.2...1, 0/1...5, 0/2...10 VDC |
Input resistance | Nom. 10 MΩ |
Output specifications
Relay output |
|
Relay functions | Setpoint, Window, Sensor error, Latch, Power and Off |
Hysteresis | 0...100% |
ON and OFF delay | 0...3600 s |
Max. voltage | 250 VRMS |
Max. current | 2 AAC or 1 ADC |
Max. AC power | 500 VA |
Sensor error reaction | Break / Make / Hold |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC LVD | TR-CU 004/2011 |
Approvals
c UL us, UL 508 | E231911 |
FM | 3025177 |
DNV Marine | TAA0000101 |
EU RO MR Type Approval | MRA000000Z |
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days.
You can expect to get a confirmed delivery date via email within 2 days after we have received your order.
As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
State-of-the-art manufacturing Our 8,500 sqm integrated and automated manufacturing campus in Denmark covers the entire value-chain from design and development to manufacturing. It allows us to design and optimize for testing and manufacturing thereby constantly driving quality up and costs down. |
Dedicated Presale / Aftersales
|
Product reliability |
Product deployment
|
Smart products
Check out our range of communication interfaces
|