9106A

 

Zone2 Ex Iec Iecex Zone2 Fmapprovedcus Zone2 Inmetro UL List CCC Kcs Mark SIL 2 SIL 3 DNV Classnk Eac Ex Mpa EAC UKCA CE Pr Rohs3
  1. Overview + -

  2. Technical details + -

  3. Accessories + -

Approvals & Certificates


ATEX certificate

IECEx certificate

UKEX certificate

FM certificate

INMETRO certificate

UL certificate

CCC certificate

KCs certificate

DNV marine certificate

ClassNK certificate

SIL certificate

EAC declaration

EAC LVD declaration

EAC Ex certificate

Metrology Pattern Approval (MPA), Russia

Supplementary documentation


EU Declaration of Conformity

UKCA Declaration of Conformity

Modbus configuration manual

Assessment

FMEDA report

ISO 13849 declaration

PR default configurations

EMC data


EMC data

Environmental Conditions

Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ PR 4500 109 x 23.5 x 131 mm
Weight approx. 250 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...13.2 Hz ±1 mm
13.2...100 Hz ±0.7 g

Common specifications

Supply

Supply voltage 19.2...31.2 VDC
Fuse 1.25 A SB / 250 VAC
Max. required power ≤ 1.1 W / ≤ 1.9 W (1 ch. / 2 ch.)
Max. power dissipation, 1 / 2 ch. ≤ 0.8 W / ≤ 1.2 W

Isolation voltage

Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply 2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation

Response time

Response time (0...90%, 100...10%) < 5 ms
Programming PR 4500 communication interfaces
Signal dynamics, input Analog signal chain
Signal dynamics, output Analog signal chain
SMART bi-directional communication frequency range 0.5...7.5 kHz
Signal / noise ratio > 60 dB
Accuracy Better than 0.1% of sel. range
mA, absolute accuracy ≤ ±16 μA
mA, temperature coefficient ≤ ±1.6 μA / °C
Effect of supply voltage change on output (nom. 24 VDC) < ±10 μA
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

Current input

Measurement range 3.5...23 mA
2-wire transmitter supply 9106A1x >16 V / 20 mA
2-wire transmitter supply 9106A2x >15 V / 20 mA
Sensor error detection: Loop break 4...20 mA < 1 mA
Input voltage drop, supplied unit < 4 V @ 23 mA
Input voltage drop, non-supplied unit < 6 V @ 23 mA

Output specifications

Current output

Signal range 3.5...23 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limit ≤ 28 mA

Passive 2-wire mA output

Effect of external 2-wire supply voltage variation < 0.005% of span / V
Max. external 2-wire supply 26 VDC

Status relay

Relay function N.C.
Programmable low setpoint 0...29.9 mA
Programmable high setpoint 0...29.9 mA
Hysteresis for setpoints 0.1 mA
Max. voltage 125 VAC / 110 VDC
Max. current 0.5 AAC / 0.3 ADC
Max. voltage - hazardous installation 32 VDC / 32 VAC
Max. current - hazardous installation 1 ADC / 0.5 AAC
of span = normal measurement range 4...20 mA

Observed authority requirements

EMC 2014/30/EU & UK SI 2016/1091
LVD 2014/35/EU & UK SI 2016/1101
ATEX 2014/34/EU & UK SI 2016/1107
RoHS 2011/65/EU & UK SI 2012/3032
EAC TR-CU 020/2011
EAC LVD TR-CU 004/2011
EAC Ex TR-CU 012/2011

Approvals

ATEX DEKRA 11ATEX0244 X
IECEx DEK 11.0084X
UKEX DEKRA 21UKEX0171X
c FM us FM16US0465X / FM16CA0213X
INMETRO DEKRA 23.0003X
c UL us, UL 61010-1 E314307
c UL us, UL 913 E233311 (only 9106xxx-U9)
CCC 2020322309003231
KCs 21_AV4BO_0169X (only 9106Axx-KCs)
EAC Ex RU C-DK.HA65.B.00355/19
DNV Marine TAA00000JD
ClassNK TA24034M
SIL SIL 2 / SIL 3 certified & fully assessed acc. to IEC 61508
Your request has been sent successfully. 0 items on your list
Your contact information

Company information

Please insert your company name.
Please insert your company address
Please insert a valid zip code
Please insert a city
Please select country

Your information

Please insert your last name
Please insert your last name
Please insert a valid email address
Please insert a valid phone number. Use only numbers.
Please insert your job title
Please read and agree with PR electronics’ Privacy Policy.
Get an answer within 24 hours

A mistake has occurred. Please call us instead

You have not added any products to your quote list
When browsing the website, you can add products to a quote list by simply clicking “Add to quote list" on the individual product pages. Once all relevant products are included, send the list to us and you will get a quotation within 24 hours. If you don't submit the list, it will be accessible on the website for 21 days. We hope you will find the functionality useful.
Thank you for requesting a quotation. We will get back to you by phone or email within 24 hours.
Service Red

If you need support, you are always welcome to contact us

Service Red
Newsletter Icon Red

Register here to receive our newsletter

Newsletter Icon Red